English
Language : 

1EGG1-1_1 Datasheet, PDF (1/2 Pages) Tyco Electronics – Smallest Filtered Power Entry Modules with Metric Fuseholders
CORCOM Product Guide
Smallest Filtered Power Entry Modules with Metric Fuseholders
GG/HG Series
UL Recognized
CSA Certified
VDE Approved
HG1/GG1
GG8
GG Series
The GG series power entry modules combine the functions
of a general purpose RFI filter with an IEC power cord
connector and single or dual metric fusing, in the smallest
possible panel space. A choice of .250” terminals or wire
leads is available for the load-side terminations.
For maximum cost effectiveness, 6 amp models should be
used for all applications rated 6 amps or less, unless the
higher performance of the 3 amp models, or the much
higher performance of the 1 amp models, is needed.
Models with C-suffix additionally incorporate a ground
choke1 to isolate the equipment chassis from external
ground at RF frequencies.
HG Series
A medical version of our GG series, these filters offer the
same compact design but reduce the line-to-ground
capacitance in order to meet UL 2601 patient care
requirements. For more information on UL2601
specification, see Appendix C.
Note: When using the models with an IEC connector,
remember that the leakage current of the companion line
cord, GA400, is more significant than that of the filter -
which may disqualify this line cord from use in patient care
applications.
Electrical Schematics
GG/GS/HG
Note 1
Specifications
Maximum leakage current,each line-to-ground
HG Models
@ 120 VAC 60 Hz:
2µA
@ 250 VAC 50 Hz:
5µA
Hipot rating (one minute):
line-to-ground
line-to-line
Operating frequency:
GG Models
.25 mA
.42 mA
1550 VAC
1450 VDC
50/60 Hz
Rated voltage (max.):
250 VAC
Fuse (not included):
Accepts one 5x20mm fuse
(-1 models) or two 5 x 20 mm
fuses (-2 models)
Minimum insertion loss in dB:
Line-to-ground in 50 ohm circuit
Current
Frequency-MHz
Rating .01 .05 .10 .15 .5 1 5
10 30
GG/GS Models
1A 12 23 29 32 41 47 50 50 55
3A – 10 15 19 30 36 48 50 53
6A – 1 4 10 16 22 36 40 50
HG Models
1A 12 23 29 32 40 40 28 22 18
3A – 10 15 19 25 26 22 21 21
6A – 4 10 14 18 18 14 14 14
LINE
LOAD
Line-to-line in 50 ohm circuit
Current
Rating
Frequency-MHz
.01 .15 .5 1 3 5 10 30
GG-C
Note 1
LINE
Note 2
LOAD
Note 2
Resistor location for reference only.
Note 1: Depicts single fuse for -1 models.
Note 2: For HG delete line-to-ground capacitors.
CAUTION: DO NOT ATTEMPT TO OPERATE A SINGLE-FUSED MODEL WITHOUT THE
FUSE DOOR IN PLACE!
GG/GS Models
1A
1
3A
1
6A
1
HG Models
1A
1
3A
1
6A
1
3 14 23 41 47 50 44
2 11 14 25 38 44 40
2 10 13 23 33 39 42
3 26 35 35 35 27 20
2 30 30 30 30 30 30
2 30 30 30 30 30 30
112
Catalog 1654001
Revised 05-07
Dimensions are in inches and
millimeters unless otherwise
specified. Values in italics
are metric equivalents.
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
USA Cust. Svc.: 1-800-468-2023
CORCOM Prods: 1-847-680-7400
Germany:
49-89-6089-0
www.corcom.com