English
Language : 

1001 Datasheet, PDF (1/1 Pages) Schurter Inc. – IEC Appliance Inlet C14, Screw-on Mounting, Rear Side, PCB Terminal
WILMAR™ Protective Relays – 1000 Series
TERMINAL STRIPS
#6 - 32 SCREWS
3 13/16
2
3
3
/4
1 /2
11/64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
Phase Failure Relays
Function: 47
• ANSI/IEEE C37.90-1978
• UL file No. E58048
• CSA file No. LR61158
Phase failure relays protect motors, equipment and
personnel from damage or injury caused by open
phase, reversed phase sequence, or low voltage in a
three phase system. Models are available for 50 and
60 Hz with voltages up to 575 volts. Motor control
switchboards are a common application.
Operation:
The contacts of the relay will close only when it
senses normal conditions of three phase power at
the proper phase sequence.
The relay contacts will remain in their normally open
position (de-energized) when voltage with incorrect
phase sequence is applied, one or more phases are
open, or at undervoltage condition.
PART NUMBER SELECTION
Part Number
PRODUCT SPECIFICATIONS
1000 Series
Nominal Voltage ............................. See Table
Voltage Drop-Out ........................... 75% to 100% of nominal, screwdriver adjustable
Pick-Up to Drop-Out Differential .... 3% approx.
Ambient Operating Temperature .... -40oC to +70oC
Temperature Drift ........................... ± 1%
Time Delay ..................................... See Curve
Output Contacts ............................. One set, normally open
PART NUMBER SELECTION
Sample Part No.
1004X
Type:
1001 = 120 V, 60 Hz, 3 phase,L-L
1007 = 208 V, 60 Hz, 3 phase, L-L
1002 = 230 V, 60 Hz, 3 phase,L-L
1012 = 300 V, 60 Hz, 3 phase, L-L
1013 = 350 V, 60 Hz, 3 phase, L-L
1003 = 380 V, 50 Hz, 3 phase, L-L
1004 = 460 V, 60 Hz, 3 phase,L-L
1005 = 525 V, 60 Hz, 3 phase,L-L
1006 = 575 V, 60 Hz, 3 Phase, L-L
Mounting:
X = Flange
Blank - Stud
Consult factory for additional models and options
Contact Ratings .............................. 10 amp at 28 VDC resistive
10 amp at 230 VAC resistive
Notes:
1. Remove screw for access to the undervoltage
adjustment.
2. Clockwise rotation of the adjustment
potentiometer will raise the drop-out voltage.
30
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)