WATER COOLED HEAT EXCHANGER UNITS
FOR MEDICAL AND INDUSTRIAL SYSTEMS
The WL500 is a re-circulating liquid to air heat exchanger that offers
dependable, compact performance by removing large amounts of
heat from a liquid circuit. The coolant is re-circulated using a high
pressure pump to assure maximum flow rate. Heat from coolant is
absorbed by a radiant heat exchanger and dissipated into the
ambient environment using brand name fan. Manual adjustments
can be made to control flow switch. Customized features are
available, however, MOQ applies.
FEATURES
• Compact design
• Reliable operation
• Adjustable flow switch
• Bypass valve protection
APPLICATIONS
• Medical imaging systems
• Photonics laser systems
• X-Ray scanning systems
• Semiconductor fabrication
SPECIFICATIONS
Performance
Cooling capacity1
500 Watts
Flow Rate
> 2.3 Ipm @ 4 bar
Operation
Coolant
Water or Water/Glycol
Operational temperature range²
5°C to 40°
Storage temperature range
-25°C to 70°C
(w/o coolant)
Humidity range
20% to 80%
Input Voltage
230 VAC
Frequency
50/60 Hz
Current Draw
1.2 Amps
Noise
< 60 dB(A)
Flow switch open
≤ 0.9 Ipm
Maximum forward pressure
2.5 bar
Physical
Dimensions (H x W x D)
37.0 x 30.7 x 15.1 cm
Weight (w/o coolant)
11 kg
Coolant Capacity
1.7 L
Couplings
Press fit (8 mm ID hose)
1. Capacity rating is given at a temperature of 25°C (77°F) for the ambient air and water outlet temperature of 13°C.
2. For ambient conditions outside this range, please contact Laird Technologies
Page 1 of 3