English
Language : 

WL2000 Datasheet, PDF (1/3 Pages) Laird Tech Smart Technology – Liquid to Air Heat Exchanger System
WL 2000
Liquid to Air Heat Exchanger System
WATER COOLED HEAT EXCHANGER UNITS
FOR MEDICAL AND INDUSTRIAL SYSTEMS
The WL2000 is a re-circulating liquid to air heat exchanger that
offers dependable, compact performance by removing large
amounts of heat from a liquid circuit. The coolant is re-circulated
using a high pressure pump to assure maximum flow rate. Heat
from coolant is absorbed by a radiant heat exchanger and dissipated
into the ambient environment using brand name fan. Manual
adjustments can be made to control flow switch. Customized
features are available, however, MOQ applies.
FEATURES
• Compact design
• Reliable operation
• Adjustable flow switch
• Bypass valve protection
APPLICATIONS
• Medical imaging systems
• Photonics laser systems
• X-Ray scanning systems
• Semiconductor fabrication
Americas: +1.919.597.7300
Europe: +46.31.420530
Asia: +86.755.2714.1166
ets.sales@lairdtech.com
www.lairdtech.com
SPECIFICATIONS
Performance
Cooling capacity1
2,000 Watts
Flow Rate
> 4.4 Ipm @ 4 bar
Operation
Coolant
Operational temperature range2
Water or Water/Glycol
10°C to 40°
Storage temperature range
-25°C to 70°C
(w/o coolant)
Humidity range
20% to 80%
Input Voltage
230 VAC
Frequency
50 Hz
Current Draw
2.1 Amps
Noise
< 70 dB(A)
Flow switch open
4.0 Ipm
Maximum forward pressure
6.7 bar
Physical
Dimensions (H x W x D)
50.5 x 30.5 x 30.0 cm
Weight (w/o coolant)
26.5 kg
Coolant Capacity
2.5 L
Couplings
Walther Type MD 006
1. Capacity rating is given at a temperature of 25°C (77°F) for the ambient air and water outlet temperature of 11°C.
Page 1 of 3