English
Language : 

WL1500 Datasheet, PDF (1/3 Pages) Laird Tech Smart Technology – Liquid to Air Heat Exchanger System
WL 1500
Liquid to Air Heat Exchanger System
Americas: +1.919.597.7300
Europe: +46.31.420530
Asia: +86.755.2714.1166
ets.sales@lairdtech.com
www.lairdtech.com
WATER COOLED HEAT EXCHANGER UNITS
FOR MEDICAL AND INDUSTRIAL SYSTEMS
The WL1500 is a re-circulating liquid to air heat exchanger that
offers dependable, compact performance by removing large
amounts of heat from a liquid circuit. The coolant is re-circulated
using a high pressure pump to assure maximum flow rate. Heat
from coolant is absorbed by a radiant heat exchanger and dissipated
into the ambient environment using brand name fan. Manual
adjustments can be made to control flow switch. Customized
features are available, however, MOQ applies.
FEATURES
• Compact design
• Reliable operation
• Adjustable flow switch
• Bypass valve protection
APPLICATIONS
• Medical imaging systems
• Photonics laser systems
• X-Ray scanning systems
• Semiconductor fabrication
SPECIFICATIONS
Performance
Cooling capacity1
1,500 Watts
Flow Rate
> 4.0 Ipm @ 4 bar
Operation
Coolant
Operational temperature range2
Water or Water/Glycol
5°C to 40°
Storage temperature range
-25°C to 70°C
(w/o coolant)
Humidity range
20% to 80%
Input Voltage
230 VAC
Frequency
50/60 Hz
Current Draw
< 2.5 Amps
Noise
68 dB(A)
Maximum forward pressure
6.0 bar
Physical
Dimensions (H x W x D)
48.1 x 39.8 x 47.9 cm
Weight (w/o coolant)
38.5 kg
Coolant Capacity
3L
Couplings
Press fit (9 mm ID hose)
1. Capacity rating is given at a temperature of 25°C (77°F) for the ambient air and water outlet temperature of 12°C.
2. For ambient conditions outside this range, please contact Laird Technologies
Page 1 of 3