Power Dissipation Ratings
Peak Pulse Current Test Waveform
100
90
50
Figure 1
Should transients occur in rapid succession, the average
power 100 dissipation result is simply the energy
(watt-seconds) per pulse times the number of pulses
per second. The power so developed must be within
UIFTQFDJmDBUJPOTTIPXOPOUIF%FWJDF3BUJOHTBOE
Specifications table for the specific device. The operating
values must be derated as shown in above.
Maximum Clamping Voltage
10000
Voltage -
VOLTS
Maximum Clamping Voltage
DHB34 Series
110 to 750V AC Rating
V571
V511 V551
1000
TA = -55 C to 85C
V661 V681
V751
V481
V441
V421
100
0.001
Figure 3
V111
V141 V131
0.01
0.1
Current - AMPS
V151
1
10
100
1000
10000
100000
V391 V351 V331 V321 V301 V271 V251 V201 V181
10
O1
Figure 2
T
T1
T2
TIME
017JSUVBM0SJHJOPG8BWF
55JNFGSPNUPPG1FBL
T13JTF5JNFY5
T2 = Decay Time
Example 'PSBOμT$VSSFOU8BWFGPSN
8μs = T13JTF5JNF
20μs = T2 = Decay Time
Repetitive Surge Capability
50,000
20,000
10,000
1
2
10
DISC SIZE 34mm
V131DHB34 - V751DHB34
5,000 102
2,000 103
1,000
104
500
105 106
200
100
50
20 INDEFINITE
10 20
Figure 4
100
1,000
IMPULSE DURATION ( μs)
10,000
NOTE: If pulse ratings are exceeded, a shift of VN(DC) (at specified current) of more than
+/-10% could result. This type of shift, which normally results in a decrease of VN(DC), may
result in the device not meeting the original published specifications, but it does not
prevent the device from continuing to function, and to provide ample protection.