English
Language : 

SB6000 Datasheet, PDF (2/2 Pages) Littelfuse – ISB is also available with adjustable protection settings
Personnel Protection
Industrial Shock-Block
SB6000 SERIES
Accessories
A
Operator Interface
(AC6000-OPI-00)
1N5339B - Termination Device
B
Axial-lead ground-check termination,
included with SB6000 series
Connection Diagram
The SB6100 is installed in-line between incoming power or existing
over-current protection device and the load.
The open-chassis SB6100 can be installed in electrical equipment and
the enclosed version is typically wall-mounted.
Incoming Power
SE-TA6 - Termination Assembly
Optional termination assembly with
terminals and mounting holes
Circuit Breaker
SE-TA6-SM Stud-Mount
Termination Assembly
Optional ground-check termination
for submersible pumps
AC6000-CART-00
Two-wheeled Cart
Optional for mounting ISB to allow for
moving the unit while power is off
AC6000-MNT-00
Mounting Frame
Optional for mounting ISB to a cart
or other surface. Included with the
AC6000-CART-00.
Ordering Information - Accessories
ACCESSORIES
AC6000-OPI-00
1N5339B
SE-TA6
SE-TA6-SM
SE-TA6ASF-WL
AC6000-CART-00
AC6000-MNT-00
REQUIREMENT
Included
Included
Optional
Optional
Optional
Optional
Optional
PAGE*
N/A
120
120
120
120
N/A
N/A
SB6100
Industrial
Shock-Block
Open-Chasis
Model
Circuit Breaker
SB6100 Industrial
Shock-Block
Enclosed Model
Specifications
Voltage Rating
See ordering information
Current Rating
100 A (continuous)
Load
3-phase, 3-wire (no neutral) or 1-phase
(line-to-line), 60 Hz
Short-Circuit
Current Rating
50,000 A
Trip Level Settings Selectable (6, 10, 20, 30, 40, 50, 60, 70, 80, 90,
100 mA), or fixed at 20 mA
Trip Time Setting
Inverse time trip curve
Enclosure
NEMA 4X, Polyester, Lockable
Operating Temperature –35°C (–31°F) to +40°C(104°F), up to +66°C (151°F)
with derating
Wiring Requirements 2/0 AWG (maximum)
Approval
GFCI: UL Listed (enclosed models) and UL
Recognized component (open-chassis models)
EGFPD: cULus Listed (enclosed models) and cURus
Recognized Component (open-chassis models);
UL1998 Compliant (revision 01 or higher);
All models CSA Certified
Dimensions
Enclosed: H 453.8 mm (17.9”);
W 406.2 mm (16.0”); D 223.3 mm (8.8”)
Open-chassis: H 455.0 mm (17.9”);
W 340.7 mm (13.4”); D 174.9 mm (6.8”)
Warranty
1 year
Littelfuse reserves the right to make product changes, without notice. Material in this document is as accurate as known at the time of publication. Visit Littelfuse.com for the most up-to-date information.
© 2017 Littelfuse Protection Relays & Controls
Littelfuse.com/IndustrialShockBlock
Rev: 4-K-061517