SE-701 Datasheet, PDF (1/1 Pages) Littelfuse – The SE-701 is a microprocessor-based
Protection Relays & Controls
Ground-Fault Protection–Grounded Systems
SE-701 Series (PGR-5701)
Ground-Fault Monitor
Simplified Circuit Diagram
A
GROUNDED B
SUPPLY
C
CT A
SE-701 SERIES
L1
(Ground-Fault Monitor)
L2
Ordering Information
Ordering Number
control power
SE-701-OU
SE-701-OD
SE-701-OT
SE-701-O3
120/240 Vac/Vdc
12/24 Vdc
48 Vdc
24 Vac
accessories
Current Transformer
PGA-0500
PMA-55, PMA-60
SE-EFVC Voltage Clamp
requirement
Required
Optional
Optional
Optional
Note: For optional conformal coating please consult factory.
© 2013 Littelfuse Protection Relays & Controls
Littelfuse.com/se-701
Description
The SE-701 is a microprocessor-based ground-fault relay for resistance-
and solidly-grounded systems. In addition to common systems, it is
uniquely suited for use on systems with significant harmonic content.
The SE-701 can provide main-plant protection, feeder-level protection,
or individual-load protection. Proper current transformer selection
provides the desired pickup range. The output contacts can be
connected for use in protective tripping circuits or in alarm indication
circuits. The analog output can be used with a PLC or a meter.
Features & Benefits
Features
BENEFITS
Adjustable pickup
(1-99%)
Trip setting based on input CT primary, allows use with
any CT. Minimum 50 mA with EFCT Series.
Adjustable time delay
(50 ms - 2.5 s)
Adjustable trip delay allows quick protection and system
coordination
Output contacts
Form A and Form B ground-fault output contacts for
operation of separate annunciation and trip circuits
Analog output
(0 - 5 V)
Allows for connecting an optional meter (PGA-0500) or a
control system
CT-Loop monitoring
Alarms when CT is not connected
Selectable DFT or peak
detection filtering
Compatible with variable-speed drives
Harmonic filtering
Eliminates nuisance tripping
Non-volatile trip
memory
Retains trip state while de-energized to simplify
troubleshooting
Microprocessor based No calibration required, saves on maintenance cost
Universal power supply
Allows operation in application where one side of PT is
faulted, provides flexibility for numerous applications
Accessories
Ground-Fault Current Transformer
A
Required current transformer model depends on
application. We offer a variety of sensitive CTs with
5- and 30-A primaries.
PGA-0500 Analog % Current Meter
B
Optional panel-mounted analog meter displays
ground-fault current as a percentage of the CT
primary rating.
Specifications
IEEE Device Numbers Ground fault (50G/N, 51G/N)
Input Voltage
See ordering information
Dimensions  H 75 mm (3.0"); W 55 mm (2.2"); D 115 mm (4.5")
Trip Level Settings
1-99% CT-Primary Rating
Trip Time Settings
0.05-2.5 s
Contact Operating Mode Selectable fail-safe or non-fail-safe
Harmonic Filtering
Standard feature
Test Button
Standard feature
Reset Button
Standard feature
CT-Loop Monitoring
Standard feature
Output Contacts
Isolated Form A and Form B
Approvals
CSA certified, UL Listed (E340889),
Analog Output
Conformally coated
Warranty
Mounting
CE (European Union), C-Tick (Australian)
0-5 V
Consult factory
5 years
DIN, Surface (standard)
Panel (with PMA-55 or PMA-60 adapter)