English
Language : 

SE-100T Datasheet, PDF (1/1 Pages) Littelfuse – The tester injects current through the window of installed
PArcocteescstoiornieRselays & Controls
Relay Testers
SE-100T SERIES
Ground-Fault-Relay Tester
Simplified Circuit Diagram
CT
Description
The SE-100T is a ground-fault-relay test unit designed to test
the current pickup level of ground-fault protection.
The tester injects current through the window of installed
ground-fault current transformers to verify the operation of
ground-fault monitors and relays.
It is used on substations, motor control centers (MCCs),
central distribution panels, switchboards, and test benches to
verify relay operation.
The SE-100T tests the entire ground-fault circuit including
current transformers, wiring, ground-fault relay and the
operation of the interrupting device. It is recommended to
test every relay and its current interrupting device annually.
Features & Benefits
FEATURES
Output Current Levels
Remote Test Input
BENEFITS
Low and high output levels to test a variety of
relays
Allows test to be initiated from another
location
Ordering Information
ORDERING NUMBER
SE-100T
CONTROL POWER
120 Vac
CT
NGR
SENSING
RESISTOR
L1
L2
NGR
MONITOR
GROUND-FAULT
MONITOR
L1
L2
SE-100T SERIES
(Ground-Fault
L1
Relay Tester)
L2
Specifications
Input Voltage
120 Vac, 60 Hz(1), 30 VA
Dimensions  H 150 mm (5.9”);
W 109 mm (4.3”);
D 100 mm (4.0”)
Output Current Levels
L0 = 0.65 ± 0.1 A
HI = 2.75 ± 1.5A
Output Voltage
6.3 Vac maximum
Approvals
CSA certified
Conformally Coated
Standard feature
Warranty
5 Year
Mounting
Surface
Note (1) Also verified at 50 Hz.
© 2014 Littelfuse Protection Relays & Controls
Rev: 4-AB-0152013213
Based on ManuaBlaRsevdisoinonM: 5a-nAu-a1l2R0e5v143