English
Language : 

PGT-0400 Datasheet, PDF (1/1 Pages) Littelfuse – Duration range is 0.1 to 9.9 s or continuous output
POWR-GARD® Relay Testing Equipment
(PGT Series)
PGT-0400 Series
Ground-Fault Relay Test Unit
INSULATED CTs
TO BE TESTED
(Phase conductor
removal not necessary)
11
12
CONTROL
POWER
RESET
1
8
3
9
5
POWR-GARD®
GROUND-FAULT RELAY
TEST UNIT
PGT- 0400
Description
The PGT-0400 is a ground-fault-relay test unit designed to
test current pickup level, time-delay and coordination of
ground-fault protection.
The tester injects current through the window of installed
ground-fault current transformers to verify the operation of
ground-fault monitors and relays.
Applications
Used on substations, motor control centers (MCCs), central
distribution panels, switchboards, and test benches to verify
relay operation.
It is recommended to test every relay annually as well as its
current interrupting device.
Features/Benefits
• The PGT-0400 tests the entire ground-fault circuit
T
including current transformers, wiring, ground-fault relay
and the operation of the interrupting device
• Current range is 0.5 to 9.9 A
• Duration range is 0.1 to 9.9 s or continuous output
• Light weight and compact for portability
Ordering Information
PGT-0400
120 Vac Control Power
Specifications
Input Voltage
Dimensions
Output Current Settings
Output Duration Settings
Output Voltage
Conformally Coated
Warranty
Mounting
84–134 Vac, 50/60 Hz, 80 VA
H 219 mm (8.6”); W 99 mm (3.9”); D 143 mm (5.6”)
0.5–9.9 A
0.1–9.9 s or continuous
5.0 Vac maximum
Standard
5 Year
Surface, Panel
© 2009 Littelfuse • POWR-GARD® Protection Relay Catalog