English
Language : 

PGR-4300 Datasheet, PDF (1/1 Pages) Littelfuse – The PGR-4300 Generator Ground-Fault Relay provides
Protection Relays & Controls
Generator & Single-Function Protection–Ground Fault
PGR-4300 SERIES (GFA300)
Generator Ground-Fault Relay
Simplified Circuit Diagram
G
Control
Power
PGR-4300
(Generator
Ground-Fault Relay)
Description
The PGR-4300 Generator Ground-Fault Relay provides
a simple method for detecting a ground-fault condition
on generators without the need for current transformers
(CTs). This greatly simplifies the installation. In addition,
it is compatible with both three- and four-pole transfer
switches. This relay also monitors the neutral-to-ground path
for continuity. The PGR-4300 is ideal for any generator or
application where there is not sufficient space to install CTs.
Features & Benefits
FEATURES
BENEFITS
No CTs required
Saves space and simplifies installation
Adjustable pickup
(100 - 1200 A)
Adjustable time delay
(0 - 1.0 s)
Output contacts
Analog output
(0 - 1 mA)
N-G continuity alarm
Adjustable trip setting provides a wide range of
protection and allows system coordination
Adjustable trip delay allows quick protection and
system coordination
Form C ground-fault output contacts for alarming
or tripping purposes
Provides means for connecting to an optional
meter (PGA-0500) or control system
Monitors neutral-to-ground integrity and alarms if
ground path becomes open circuit
Passive filtering
Eliminates nuisance tripping
Accessories
PGA-0500 Analog % Current Meter
Optional panel-mounted analog meter
displays ground-fault current as a
percentage of the set-point.
Ordering Information
ORDERING NUMBER
CONTROL POWER
PGR-4300-12
PGR-4300-24
PGR-4300-120
12 Vdc
24 Vdc
120 Vac
ACCESSORIES
REQUIREMENT
PGA-0500
Optional
PMA-55
Optional
PMA-60
Optional
Note: For optional conformal coating please consult factory.
Specifications
IEEE Device Numbers
Ground Fault (50G/N, 51G/N)
Input Voltage
See ordering information
Dimensions H 75 mm (3.0”); W 55 mm (2.2”); D 115 mm (4.5”)
Trip Level Settings
100-1200 A
Trip Time Delay Settings 0-1.0 s
Contact Operating Mode Non-fail-safe
Test Button
Reset Button
Output Contacts
Analog Output
Conformally Coated
Approvals
Warranty
Mounting
Local
Local and remote
Form C
0-1 mA
Consult factory
UL Listed (E183688)
5 years
DIN, Surface (standard)
Panel (with PMA-55 or PMA-60 adapter)
© 2015 Littelfuse Protection Relays & Controls
Littelfuse.com/pgr-4300
Rev: 4-A-092315
Based on Manual Rev: 3-A-073115