English
Language : 

KLDR Datasheet, PDF (1/5 Pages) Littelfuse – CLASS CC KLDR SERIES FUSES
POWR-GARD® Fuse Datasheet
Class CC KLDR Series FUSES
600 VAC • 300 VDC • Time-Delay • 1/10-30 A
Description
KLDR fuses are time-delay fuses designed to protect control
transformers, sol­en­ oids and similar inductive components
with high magn­ et­iz­ing currents during the first half-cycle.
They provide ex­cel­lent protection of motor branch circuits
cont­ain­ing IEC or NEMA rated motor cont­roll­ers or
contactors.
Features/Benefits
• Meets UL and CSA standards
• Class CC fuses are the smallest 600 V, 200,000 A.I.R.
fuses approved for branch circuit protection
• Rejection feature prevents use of fuses with lower
interrupting ratings or voltage ratings when used with
corresponding fuse holders
• Extremely current limiting reduces damage caused by
heating and magnetic effects of short-circuit currents
Applications
• Transformer Protection
Specifications
Voltage Rating
Amperage Rating
Interrupting Rating
Material
Fuse Weight
Approvals
Environmental
Country of Origin
AC: 600 V
DC: 300 V
1/10 – 30 A
AC: 200 kA rms symmetrical
DC: 20 kA
Body: Melamine
Caps: Nickel-plated Bronze
.019 lb (8.62g)
AC: S tandard 248-4, Class CC
UL Listed 1/10-30 A (File: E81895)
CSA Certified 1/10-30 A (File: LR29862)
DC: Littelfuse self-certified
RoHS Compliant
Mexico
Ordering Information
1/10
1/8
/15 100
3/16
2/10
1/4
3/10
4/10
1/2
AMPERAGE ratings
6/10
1 8/10
4 1/2
3/4
2
5
8/10
2 1/4
5 6/10
1
2 1/2
6
1 1/8
2 8/10
6 1/4
1 1/4
3
7
1 4/10
3 2/10
7 1/2
1 1/2
3 1/2
8
1 6/10
4
9
10
12
15
17 1/2
20
25
30
—
—
AMPERAGE
10
Part number
KLDR 10
ORDERING number
KLDR010.TXP
Web Resources
For additional informations, visit:
Littelfuse.com/kldr
Recommended Fuse Holders
L60030C Series
LPSC Touch-Safe Series
Dimensions Inches (mm)
1.50
(38.1)
0-30 A
.25
(6.4)
.50
(12.7)
.41
(10.3)
.125
(3.2)
Littelfuse.com
1 of 5
© 2013 Littelfuse POWR-GARD® Products
Rev: 032113