English
Language : 

469 Datasheet, PDF (1/4 Pages) Littelfuse – Surface Mount Fuses
Surface Mount Fuses
Ceramic Fuse > 469 Series
469 Series – 1206 Slo-Blo® Fuse
Agency Approvals
AGENCY
AGENCY FILE NUMBER
E10480
LR29862 (Pending)
AMPERE RANGE
1A – 8A
1A – 8A
Electrical Characteristics for Series
% of Ampere
Rating
100%
200%
300%
800%
Ampere
Rating
1A – 8A
1A – 8A
1A – 8A
1A – 8A
Opening Time at 25ºC
4 hours, Minimum
1 sec., Min.; 120 secs., Max.
0.1 sec., Min.; 3 secs., Max.
0.002 sec., Min.; 0.05 sec., Max.
Description
The 469 Series is a 100% Lead-free, RoHS compliant and
Halogen-free fuse series designed specifically to provide
over-current protection to circuits that operate under high
working ambient temperature up to 150ºC.
The general design ensures excellent temperature stability
and performance reliability.
The high I²t values which are typical in the Littelfuse
Ceramic fuse family, ensure high inrush current withstand
capability.
Features
t 0QFSBUJOH5FNQFSBUVSF
from -55ºC to +150ºC
t -FBEGSFF 3P)4
compliant and Halogen-
free
t 4VJUBCMFGPSCPUIMFBEFE
and lead-free reflow /
wave soldering
Applications
t "VUPNPUJWF&MFDUSPOJDT
t -$%%JTQMBZT
t 4FSWFST
t /PUFCPPL$PNQVUFST
t 1SJOUFST
t 4DBOOFST
t %BUB.PEFNT
t (BNJOH$POTPMFT
Electrical Specifications by Item
Ampere
Rating
(A)
Amp
Code
1
001.
1.25 1.25
1.5
01.5
2
002.
2.5 02.5
3
003.
3.5 03.5
4
004.
5
005.
6
006.
7
007.
8
008.
Max.
Voltage
Rating (V)
63
63
63
63
32
32
32
32
32
24
24
24
Interrupting Rating
50 A @ 63 V DC
50 A @ 32 V DC
60 A @ 32 V DC
60 A @ 24 V DC
Nominal
Resistance
(Ohms)2
0.052
0.035
0.028
0.021
0.017
Nominal Nominal Voltage
Melting I2t Drop At Rated
(A2Sec.)3
Current (V)4
$0.*/(400/
3.560
5.620
9.410
14.400
23.720
0.236
0.216
0.274
0.216
0.233
Nominal Power
Dissipation At
Rated Current (W)
0.944
1.080
1.640
1.510
1.860
Agency Approvals
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
pending
/PUFT
1. AC Interrupting Rating tested at rated voltage with unity power factor. DC Interrupting
Rating tested at rated voltage with time constant < 0.8 msec.
/PNJOBM3FTJTUBODFNFBTVSFEXJUISBUFEDVSSFOU
/PNJOBM.FMUJOH*¤UNFBTVSFEBUNTFDPQFOJOHUJNF
/PNJOBM7PMUBHF%SPQNFBTVSFEBUSBUFEDVSSFOUBGUFSUFNQFSBUVSFIBTTUBCJMJ[FE
Devices designed to carry rated current for 4 hours minimum. It is recommended that
devices be operated continuously at no more than 80% rated current. See “Temperature
Rerating Curve”for additional rerating information.
Devices designed to be mounted with marking code facing up.
© 2009 Littelfuse, Inc.
Specifications are subject to change without notice.
Please refer to www.littelfuse.com/series/469.html for current information.
Revised: September 1, 2009
469 Series