English
Language : 

0232001_1 Datasheet, PDF (1/4 Pages) Littelfuse – 5 x 20 mm Medium-Acting Fuse
Axial Lead and Cartridge Fuses
Designed to METI Standard
5 x 20 mm Medium-Acting Fuse 232 Series
• Designed to Japanese Standard JIS C6575.
• Available in Cartridge, Axial and Radial Lead Format.
• Available in ratings of 1A to 10A.
• Improved I2 t
ELECTRICAL CHARACTERISTICS:
% of Ampere
Rating
Opening
Time
130%
1 hour, Minimum
160%
1 hour, Maximum
200%
2 minutes, Maximum
INTERRUPTING RATING:
1A-5A 10,000A @ 125VAC, 0.7-0.8 power factor
6.3A-10A 300A @ 125VAC, 0.7-0.8 power factor
100 amperes @ 250 VAC, 0.7-0.8 power factor
ORDERING INFORMATION:
Catalog
Number
0232 001.
0232 1.25
0232 01.6
0232 002.
0232 02.5
0232 003.
0232 3.15
0232 004.
0232 005.
0232 06.3
0232 008.
0232 010.
Ampere
Rating
1
1.25
1.6
2
2.5
3
3.15
4
5
6.3
8
10
Voltage
Rating*
125/250
125/250
125/250
125/250
125/250
125/250
125/250
125/250
125/250
125/250
125/250
125/250
*To order 125V rating, add part number suffix X125
Nominal
Resistance
Cold Ohms
0.092
0.069
0.054
0.037
0.029
0.023
0.022
0.017
0.013
0.010
0.0076
0.006
Nominal
Melting I2t
A2 Sec
1.373
4.114
6.957
8.253
13.876
17.187
21.958
37.733
56.721
90.413
182.578
290.664
ENVIRONMENTAL SPECIFICATIONS:
Operating temperature: -55˚C to 125˚C
Thermal Shock: MIL-STD-202F Method 107G, Test Condition B: (5
cycles –65°C to +125°C)
Vibration: MIL-STD-202F Method 201A
Humidity: MIL-STD-202F Method 103B, Test Condition A. high relative
humidity (95%) and elevated temperature (40°C) for 240 hours.
Salt Spray: MIL-STD-202F Method 101D, Test Condition B
PHYSICAL SPECIFICATIONS:
Material: Body: Glass
Cap: Nickel Plated Brass
Leads: Tin Plated Copper
Terminal Strength: MIL-STD-202F Method 211A,
Test Condition A
Solderability: Reference IEC 60127 Second Edition 2003-01 Annex A
Product Marking: Cap 1: current and voltage rating.
Cap 2: Agency approval markings.
Packaging: Available in Bulk (V=5, H=100, M=1000 pcs/pkg) or on
Tape/Reel (MRET1=1000 pcs/reel).
434