LTC1647-1/
LTC1647-2/LTC1647-3
PIN FUNCTIONS
VCC1 (LTC1647-3): Channel 1 Positive Supply Input.
The supply range for normal operation is 2.7V to 16.5V.
The supply current, ICC1, is typically 1mA. Channel 1’s
undervoltage lockout (UVLO) circuit disables GATE 1 until
the supply voltage at VCC1 is greater than VLKO (typically
2.45V). GATE 1 is held at ground potential until UVLO
deactivates. If ON1 is high and VCC1 is above the UVLO
threshold voltage, GATE 1 is pulled high by a 10μA current
source. If VCC1 falls below (VLKO – VLKH), GATE 1 is pulled
immediately to ground. The internal reference and the
common charge pump are powered from the higher of
the two VCC inputs, VCC1 or VCC2.
VCC2 (LTC1647-3): Channel 2 Positive Supply Input. See
VCC1 for functional description.
VCC: The Common Positive Supply Input for the LTC1647-1
and the LTC1647-2. VCC1 and VCC2 are internally connected
together.
GND: Chip Ground.
ON1: Channel 1 ON Input. The threshold at the ON1 pin is
set at 1.29V with 70mV hysteresis. If UVLO and the circuit
breaker of channel 1 are inactive, a logic high at ON1 enables
the 10μA charge pump current source, pulling the GATE
1 pin above VCC1. If the ON1 pin is pulled low, the GATE 1
pin is pulled to ground by a 50μA current sink.
ON1 resets channel 1’s electronic circuit breaker by pulling
ON1 low for greater than one tRESET period (50μs). A
low-to-high transition at ON1 restarts a normal GATE 1
pull-up sequence.
ON2: Channel 2 ON Input. See ON1 for functional
description.
FAULT1: Channel 1 Open-Drain Fault Status Output. FAULT1
pin pulls low after 0.3μs (tFAULT) if the circuit breaker
measures greater than 50mV across the sense resistor
connected between VCC1 and SENSE 1. If FAULT1 pulls
low, GATE 1 also pulls low. FAULT1 remains low until ON1
is pulled low for at least one tRESET period.
FAULT2: Channel 2 Open-Drain Fault Status Output. See
FAULT 1 for functional description.
SENSE1: Channel 1 Circuit Breaker Current Sense Input.
Load current is monitored by a sense resistor connected
between VCC1 and SENSE 1. The circuit breaker trips if the
voltage across the sense resistor exceeds 50mV (VCB). To
disable the circuit breaker, connect SENSE 1 to VCC1. In
order to obtain optimum performance, use Kelvin-sense
connections between the VCC and SENSE pins to the
current sense resistor.
SENSE2: Channel 2 Circuit Breaker Current Sense Input.
See SENSE 1 for functional description.
GATE1: Channel 1 N-channel MOSFET Gate Drive Output.
An internal charge pump guarantees at least 10V of gate
drive from a 5V supply. Two Zener clamps are incorporated
at the GATE 1 pin; one Zener clamps GATE 1 approximately
15V above VCC and the second Zener clamps GATE 1
appoximately 28V above GND. The rise time at GATE 1 is
set by an external capacitor connected between GATE 1
and GND and an internal 10μA current source provided
by the charge pump. The fall time at GATE 1 is set by
the 50μA current sink if ON1 is pulled low. If the circuit
breaker is tripped or the supply voltage hits the UVLO
threshold, a 50mA current sink rapidly pulls GATE 1 low.
An external 23V Zener from GATE1 to GND is required for
supply voltages (VCC1) greater than 10V.
GATE2: Channel 2 N-channel MOSFET Gate Drive Output.
See GATE 1 for functional description.
NC: No Connection.
1647fa
8