English
Language : 

J85480S1 Datasheet, PDF (4/10 Pages) Lineage Power Corporation – Compact Power Line Shelves
DC Output Connections
 Each Output Bus is rated for
100A and up to 2 gage two-
hole lugs.
 M6 nuts with conical washers
provided.
 Touch-Safe plastic covers
around output buses.
Torque to 50 in-lb
(5.7 nm)
DC Split Output Bus Option
 Split Vout ( - ) buses on either
side of the shelf. Vout ( + ) is
common to both sections.
 +5V bias maintains I2C
communications even during
a feeder fault.
 Multiple shelves may not be
paralleled together.
Rectifier
or
PEM
Torque to 50 in-lb
(5.7 nm)
Bus A
Output
Bus B
Output
Two DC Output
Busses
Feeder-A Feeder-B
AC or DC Input
Feeds
Controllerless Operation
 Lists 4 and 6 ship with a jumper
installed on connector J1 pins 21 and
23. This allows the shelf to be powered
without a controller. Remove this
jumper if controller cable installed.
 CP843A controller ships with a
connector that plugs into J1 on a List 1
shelf activating the controller.
 Lists 7, 9 and 14 require cc848836107
connector be installed in J1 to allow the
shelf to power up without a controller.
L7, L9, L14 P1 Mating connector (pin out is standard 40 position like L4)
Type
Individual wire set
Housing
AMP 102387-9 RoHS
Mating pin
20-24 awg: 6-87523-9
Crimping tool
91517-1
22-26 awg: 6-87756-8
91517-1
40 position Ribbon cable
AMP 1658621-9 e/w 499252-1 (strain relief) RoHS
This connector set is different because it can accept either a ribbon cable or an individual wire mate.
COMPACT POWER LINE SHELVES – MODEL J85480S1
4 of 10