English
Language : 

LAH50-P_07 Datasheet, PDF (2/3 Pages) LEM – Current Transducer
Current Transducer LAH 50-P
Isolation characteristics
Vd
Rms voltage for AC isolation test, 50/60 Hz, 1 mn
5
kV
V
Impulse withstand voltage 1.2/50 µs
w
12
kV
Ve
Partial discharge extinction voltage rms @ 10pC
>2
kV
Min
dCp Creepage distance 5)
11.75
mm
dCl Clearance distance 5)
11.75
mm
CTI Comparative Tracking Index (Group I)
175
Application examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
• Over voltage category OV 3
• Pollution degree PD2
• Non-uniform field
dCp, dCI
Single isolation
Reinforced isolation
EN 50178
Rated isolation voltage
1000 V
500 V
IEC 61010-1
Nominal voltage
1000 V
500 V
Note: 5) On PCB with soldering pattern UTEC93-703.
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer's
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
071108/9
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 2/3
w w w .lem.com