English
Language : 

HX-05-P Datasheet, PDF (2/3 Pages) LEM – Current Transducer HX 03..50-P
Current Transducer HX 03..50-P
Isolation characteristics
Vd
Rms voltage for AC isolation test, 50 Hz, 1 min
> 3
kV
Ve
Partial discharge extinction voltage rms @ 10 pC
≥ 1
kV
Vw
Impulse withstand voltage 1.2/50 µs
≥ 6
kV
dCp Creepage distance
dCI Clearance distance
CTI Comparative Tracking Index (group I)
≥ 5.5
mm
≥ 5.5
mm
≥ 600
Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
●● Over voltage category OV 3
●● Pollution degree PD2
●● Non-uniform field
dCp, dCI,Vw
Basic insulation
Reinforced insulation
EN 50178
Rated insulation voltage
600 V
300 V
IEC 61010-1
Nominal voltage
600 V
150 V
Safety
This transducer must be used in electric/electronic equipment with respect
to applicable standards and safety requirements in accordance with the
manufacturer’s operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
110523/14 .
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 2/3
www.lem.com