English
Language : 

TT50-SD Datasheet, PDF (1/4 Pages) LEM – AC Current transformer
AC Current transformer TT 50-SD
Split core transducer for the electronic measurement of AC waveform
currents, with galvanic isolation between the primary circuit (power) and
the secondary circuit (measurement).
IPN = 50 A
Electrical data
IPN
Primary nominal current rms
IOUT
Output current
VSZ
Output clamping voltage
ÎP
Overload capability - continuous
- 1 min
50
At
16.66
mA
7.5
V
100
A
1200
A
Performance data
εXG
L
TCIOUT
∆ϕ
BW
Overall accuracy @ IPN, TA = 25°C
Linearity error
Temperature coefficient of IOUT
Phase shift
Frequency bandwidth (± 1dB)
<±1
%
0.1
%
60
ppm/K
1.5° ± 1°
50/60
Hz
General data
TA
TS
m
IPxx
Ambient operating temperature
Ambient storage temperature
Mass
Protection degree
- 25 .. + 70 °C
- 30 .. + 90 °C
80
g
IP40
Isolation characteristics
Vb
Rated isolation voltage rms1)
300
V
with IEC 61010-1 standards and following conditions :
- Reinforced isolation
- Over voltage category CAT III
- Pollution degree PD2
- Heterogeneous field
Vd
Rms voltage for AC isolation test 2), 50Hz, 1min
Vw
Impulse withstand voltage 1.2/50ms
dCp
Creepage distance
3.5
kV
6.5
kV
6
mm
dCl
Clearance distance
6
mm
CTI
Comparative tracking index (Group I)
600
Notes :
1) If insulated cable is used for the primary circuit, the voltage category
could be improved according to the primary cable insulation category
(please refer to the cable manufacturer's indications)
2) between primary (completely filling the hole) and secondary.
Features
• Split core type
• Ø 8 mm sensing aperture for non-
contact measurement
• Cable output (1m)
• Isolated plastic case recognized
according to UL 94-V0.
Advantages
• High accuracy and low phase shift
• High isolation between primary and
secondary circuits
• Compact case
• Cost-effective solution
• Easy installation.
Applications
• Power meters
Current measurement for active
power calculation
• Energy sub-meters
For energy efficiency monitoring,
consumption analysis and costs
allocation
• Power quality monitoring
• Condition monitoring
(e.g. motor loads such as
conveyers, pumps or HVAC)
• Distributed measurement systems
Application domain
• Energy and Automation
0 7 111 5 / 5
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/4
www.lem.com