|
NNC-10GFP Datasheet, PDF (1/2 Pages) LEM – Current Transducer | |||
|
Current Transducer NNC-10..40GFP
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 50 .. 600 A
Electrical data
Primary nominal
DC current
IPN (A)
100
200
300
400
Primary current
measuring range
IP (A)
± 300
± 600
± 900
± 1000
Type
NNC-10GFP
NNC-20GFP
NNC-30GFP
NNC-40GFP
VC
I
C
Vd
R
IS
VOUT
R
OUT
RL
Supply voltage (±5 %)
±15
V
Current consumption
<±18
mA
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn 2.5
kV
Isolation resistance @ 500 VDC
> 1000 Mâ¦
Output voltage @ ± IPN, RL = 10 kâ¦, TA = 25°C
±4
V
Output internal resistance
< 100
â¦
Load resistance
10
kâ¦
Accuracy - Dynamic performance data
X
εL
V
OE
VOH
VOT
ε TC G
tr
Accuracy @ T = 25°C (without offset)
A
Linearity1) (0 .. ± IPN)
Electrical offset voltage, T = 25°C
A
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x I
PN
Thermal drift of VOE NNC-10GFP
NNC-20..40GFP
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
<±1
<±1
<±30
% of I
PN
% of IPN
mV
<±35
<±2
<±1
<±0.1
<7
mV
mV/K
mV/K
%/K
µs
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
m
Mass
-10 .. +80 °C
-15 .. +85 °C
50
g
Features
⢠Hall effect measuring principle
⢠Galvanic isolation between primary
and secondary circuit
⢠Isolation voltage 2500V
⢠Low power consumption
â¢
Extended
measuring
range
(3
x
I)
PN
Advantages
⢠Small size and space saving
⢠Only one design for wide current
ratings range
⢠High immunity to external
interference.
Applications
⢠AC variable speed drives
⢠Battery supplied applications
⢠Uninterruptible Power Supplies
(UPS)
⢠DC motor drives
⢠Switched Mode Power
Supplies(SMPS)
⢠Power supplies for welding
applications
Notes : 1) Linearity data exclude the electrical offset.
LEM Components
050113/1
www.lem.com
|
▷ |