English
Language : 

LV100-300_03 Datasheet, PDF (1/2 Pages) LEM – Voltage Transducer
Voltage Transducer LV 100-300
For the electronic measurement of voltages : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high voltage)
and the secondary circuit (electronic circuit).
VPN = 300 V
Electrical data
VPN Primary nominal r.m.s. voltage
VP Primary voltage, measuring range
IPN Primary nominal r.m.s. current
RM Measuring resistance
with ± 15 V
@ ± 300 V max
@ ± 450 V max
ISN Secondary nominal r.m.s. current
K N Conversion ratio
VC Supply voltage (± 5 %)
IC
Current consumption
Vd R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
Accuracy - Dynamic performance data
εX G
L
Overall Accuracy @ VPN , TA = 25°C
Linearity
IO
Offset current @ IP = 0, TA = 25°C
IOT
Thermal drift of IO
0°C .. + 70°C
tr
Response time @ 90 % of VPN
General data
TA
Ambient operating temperature
TS Ambient storage temperature
N
Turns ratio
P
Total primary power loss
R 1 Primary resistance @ TA = 25°C
R S Secondary coil resistance @ TA = 70°C
m Mass
Standards
300
V
0 .. ± 450
V
33.33
mA
RM min
RM max
0
170 Ω
0
90 Ω
50
mA
300 V / 50 mA
± 15
V
10 + IS
mA
6
kV
± 0.7
%
< 0.1
%
Typ Max
± 0.2 mA
± 0.2 ± 0.3 mA
80
µs
0 .. + 70
°C
- 25 .. + 85
°C
3000 : 2000
10
W
9
kΩ
60
Ω
850
g
EN 50178
Features
• Closed loop (compensated) voltage
transducer using the Hall effect
• Insulated plastic case recognized
according to UL 94-V0
• Primary resistor R 1 incorporated into
the housing.
Advantages
• Excellent accuracy
• Very good linearity
• Low thermal drift
• High immunity to external
interference.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Uninterruptible Power Supplies
(UPS)
• Power supplies for welding
applications.
LEM Components
030415/3