English
Language : 

LTS-6-NP Datasheet, PDF (1/4 Pages) LEM – Current Transducer LTS 6-NP
Current Transducer LTS 6-NP
For the electronic measurement of currents: DC, AC, pulsed..., with
galvanic separation between the primary circuit and the secondary
circuit.
IP N = 6 At
Electrical data
IP N
IP M
IP
Vout
G
NS
RL
RI M
TCRI M
UC
IC
Primary nominal RMS current
Primary current, measuring range
Overload capability
Output voltage (analog) @ IP
@ IP = 0
Sensitivity
Number of secondary turns (±0.1 %)
Load resistance
Internal measuring resistance (±0.5 %)
Temperature coefficient of RI M
Supply voltage (±5 %)
Current consumption @ UC = 5 V Typical
Accuracy - Dynamic performance data
6
At
0 … ±19.2
At
250
At
2.5 ±(0.625 × IP/ IP N) V
2.5 1)
V
104.16
mV/A
2000
≥ 2
kΩ
208.33
Ω
< 50
ppm/K
5
V
28 + IS 2) (Vout/RL) mA
X
εL
TCVout
TCG
VO M
tra
tr
BW
Accuracy @ IP N, TA = 25 °C
Accuracy with RI M,@ IP N, TA = 25 °C
Linearity error
±0.2
±0.7
< 0.1
Typ Max
Temperature coefficient of Vout @ IP = 0 −10 ... +85 °C 80 200
−40 ... −10 °C
250
Temperature coefficient of G −40 ... +85 °C
50 3)
Magnetic offset voltage @ IP = 0,
after an overload of 3 × IP N
±0.5
after an overload of 5 × IP N
±2.0
after an overload of 10 × IP N
±2.0
Reaction time @ 10 % of IP N
< 100
Step response time to 90 % of IP N 4)
< 400
Frequency bandwidth (0 ... −0.5 dB)
DC … 100
(−0.5 ... 1 dB)
DC … 200
%
%
%
ppm/K
ppm/K
ppm/K
mV
mV
mV
ns
ns
kHz
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
m
Mass
Standards
Notes: 1) Absolute value @ TA = 25 °C, 2.475 < Vout < 2.525
2) IS = IP/ NS
3) Only due to TCRI M
4) For a di/dt = 15 A/μs.
−40 … +85
°C
−40 … +100
°C
10
g
EN 50178: 1997
IEC 60950-1: 2001
Features
●● Closed loop (compensated)
current transducer using the Hall
effect
●● Unipolar supply voltage
●● Insulating plastic case recognized
according to UL 94-V0
●● Compact design for PCB
mounting
●● Incorporated measuring
resistance
●● Extended measuring resistance.
Advantages
●● Excellent accuracy
●● Very good linearity
●● Low temperature drift
●● Optimized response time
●● Wide frequency bandwidth
●● No insertion losses
●● High immunity to external
interference
●● Current overload capability.
Applications
●● AC variable speed drives and
servo motor drives
●● Static converters for DC motor
drives
●● Battery supplied applications
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Power supplies for welding
applications.
Application domain
●● Industrial.
N° 97.37.09.000.0
25August2017/version 21
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
Page 1/4