LT4000-S Datasheet, PDF (1/2 Pages) LEM – Current Transducer LT 4000-S | |||
|
Current Transducer LT 4000-S
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 4000 A
Electrical data
I
Primary nominal r.m.s. current
PN
IP
Primary current, measuring range
R
Measuring resistance
M
with ± 24 V
@ ± 4000 A
max
@ ± 6000 A max
ISN
Secondary nominal r.m.s. current
K N Conversion ratio
VC Supply voltage (± 5 %)
IC
Current consumption
Vd
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
Accuracy - Dynamic performance data
εX G
L
Overall accuracy @ IPN , TA = 25°C
Linearity
I
O
IOT
tr
di/dt
f
Offset current @ I = 0, T = 25°C
P
A
Thermal drift of IO
Response time 1) @ 90 % of IP max
di/dt accurately followed
Frequency bandwidth (- 1 dB)
- 25°C .. + 70°C
General data
TA
Ambient operating temperature
T
Ambient storage temperature
S
R S Secondary coil resistance @ TA = 70°C
m
Mass
Standards 2)
4000
A
0 .. ± 6000
A
R
M min
R
M max
0
10
â¦
0
2
â¦
800
mA
1 : 5000
± 24
V
35 (@ ± 24 V) + IS mA
6
kV
± 0.5
%
< 0.1
%
Typ Max
± 0.8 mA
± 0.6 ± 0.8 mA
<1
> 50
DC .. 100
µs
A/µs
kHz
- 25 .. + 70
°C
- 40 .. + 85
°C
15
â¦
6
kg
EN 50178
Features
â¢Closed loop (compensated) current
transducer using the Hall effect
â¢Insulated plastic case recognized
according to UL 94-V0.
Advantages
â¢Excellent accuracy
â¢Very good linearity
â¢Low temperature drift
â¢Optimized response time
â¢Wide frequency bandwidth
â¢No insertion losses
â¢High immunity to external
interference
â¢Current overload capability.
Applications
â¢AC variable speed drives and servo
motor drives
â¢Static converters for DC motor drives
â¢Battery supplied applications
â¢Uninterruptible Power Supplies
(UPS)
â¢Switched Mode Power Supplies
(SMPS)
â¢Power supplies for welding
applications.
Notes : 1) With a di/dt of 100 A/µs
2) A list of corresponding tests is available
LEM Components
980728/8