English
Language : 

LF305-S_11 Datasheet, PDF (1/3 Pages) LEM – Current Transducer
Current Transducer LF 305-S
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 300 A
16167
Electrical data
IPN
Primary nominal current rms
IPM
Primary current, measuring range
RM
Measuring resistance @
with ± 12 V @ ± 300 A max
@ ± 500 A max
with ± 15 V @ ± 300 A max
@ ± 500 A max
with ± 20 V @ ± 300 A max
@ ± 500 A max
ISN
Secondary nominal current rms
KN
Conversion ratio
VC
Supply voltage (± 5 %)
IC
Current consumption
300
A
0 .. ± 500
A
TA = 70°C
R R M min M max
0
37
TA = 85°C
R R M min M max
0 35 Ω
0
10 0 8 Ω
0
56 0 54 Ω
0
21 0 19 Ω
0
88 0 86 Ω
0
40 0 38 Ω
150
mA
1 : 2000
± 12 .. 20
V
26 (@± 20V)+ IS mA
Accuracy - Dynamic performance data
XεG
L
IO
IOM
IOT
tra
tr
di/dt
BW
Overall accuracy @ IPN , TA = 25°C
Linearity error
± 0.5
< 0.1
Typ Max
Offset current @ IP = 0, TA = 25°C
Magnetic offset current 1) @ IP=0 and specified RM
after an overload of 3 x IPN
Temperature variation of IO
- 40°C .. + 85°C ± 0.2
- 10°C .. + 70°C ± 0.1
± 0.2
± 0.2
± 0.7
± 0.3
Reaction time to 10 % of IPN
Response time 2) to 90 % of IPN step
di/dt accurately followed
< 500
< 1
> 100
Frequency bandwidth (- 1 dB)
DC .. 100
%
%
mA
mA
mA
mA
ns
µs
A/µs
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
RS
Secondary coil resistance @ TA = 70°C
TA = 85°C
m
Mass
Standards
- 40 .. + 85
°C
- 40 .. + 85
°C
30
Ω
32
Ω
95
g
EN 50178:1997
Features
●● Closed loop (compensated)
current transducer using the Hall
effect
●● Isolated plastic case recognized
according to UL 94-V0.
Advantages
●● Excellent accuracy
●● Very good linearity
●● Low temperature drift
●● Optimized response time
●● Wide frequency bandwidth
●● No insertion losses
●● High immunity to external
interference
●● Current overload capability.
Applications
●● AC variable speed drives and
servo motor drives
●● Static converters for DC motor
drives
●● Battery supplied applications
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Power supplies for welding
applications.
Application domains
●● Industrial.
Notes:1) The result of the coercive field of the magnetic circuit
2) With a di/dt of 100 A/µs.
110210/11
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com