English
Language : 

LF305-S_06 Datasheet, PDF (1/3 Pages) LEM – Current Transducer
Current Transducer LF 305-S
For the electronic measurement of currents: DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 300 A
Electrical data
IPN Primary nominal current rms
IPM Primary current, measuring range
RM Measuring resistance
with ± 12 V
with ± 15 V
with ± 20 V
@ ± 300 A max
@ ± 500 A max
@ ± 300 A max
@ ± 500 A max
@ ± 300 A max
@ ± 500 A max
ISN Secondary nominal current rms
K N Conversion ratio
VC Supply voltage (± 5 %)
IC
Current consumption
16167
Accuracy - Dynamic performance data
εX G
L
Overall accuracy @ IPN , TA = 25°C
Linearity error
IO
IOM
IOT
tra
tr
di/dt
BW
Offset current @ IP = 0, TA = 25°C
Magnetic offset current 1) @ IP = 0 and specified RM,
after an overload of 3 x IPN
Temperature variation of IO
- 10°C .. + 70°C
Reaction time @ 10 % of IPN
Response time 2) to 90 % of IPN step
di/dt accurately followed
Frequency bandwidth (- 1 dB)
General data
TA
Ambient operating temperature
TS Ambient storage temperature
R S Secondary coil resistance @ TA = 70°C
m Mass
Standards
300
A
0 .. ± 500
A
RM mini
RM maxi
0
39 Ω
0
12 Ω
0
58 Ω
0
22 Ω
15
93 Ω
15
45 Ω
150
mA
1 : 2000
± 12 .. 20
V
26 (@±20V) + IS mA
± 0.4
%
< 0.1
%
Typ Maxi
± 0.20 mA
± 0.08 mA
± 0.1 ± 0.30 mA
< 500
<1
> 100
DC .. 100
ns
µs
A/µs
kHz
- 10 .. + 70
°C
- 25 .. + 85
°C
25
Ω
95
g
EN 50178: 1997
Features
• Closed loop (compensated) current
transducer using the Hall effect
• Isolated plastic case recognized
according to UL 94-V0.
Advantages
• Excellent accuracy
• Very good linearity
• Low temperature drift
• Optimized response time
• Wide frequency bandwidth
• No insertion losses
• High immunity to external
interference
• Current overload capability.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
Application domain
• Industrial.
Notes: 1) The result of the coercive field of the magnetic circuit
2) With a di/dt of 100 A/µs.
061031/7
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
page 1/3
www.lem.com