English
Language : 

LF2005-S_11 Datasheet, PDF (1/3 Pages) LEM – Current Transducer
Current Transducer LF 2005-S
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 2000 A
Electrical data
16103
IPN Primary nominal current rms
2000
A
IPM Primary current, measuring range @ ± 24 V
0 .. ± 3000
A
RM Measuring resistance @ TA = 70 °C
TA = 85 °C
RM R min M max
R R M min M max
with ± 15 V @ ± 2000 A max 0 8
07
Ω
@ ± 2200 A max 0 5
04
Ω
with ± 24 V @ ± 2000 A max 5 29
13 28 Ω
@ ± 3000 A max 5 11 @ ± 2800 A 13 13
Ω
ISN Secondary nominal current rms
400
mA
KN Conversion ratio
1 : 5000
VC Supply voltage (± 5 %)
± 15 .. 24
V
IC
Current consumption (± 1)
33 (@ ± 24 V) + IS mA
Accuracy - Dynamic performance data
X
ε
L
Accuracy @ IPN, TA = 25°C
Linearity error
± 0.3
< 0.1
Typ Max
IO
Offset current @ IP = 0, TA = 25°C
IOM Magnetic offset current @ IP = 0 and specified RM
after an overload of 3 x IPN
IOT
Temperature variation of IO
- 25°C .. + 85°C ± 0.2
- 40°C .. - 25°C
± 0.5
± 0.2
± 0.5
± 1.5
tr
Response time 1) to 90 % of IPN step
di/dt di/dt accurately followed
< 1
> 50
BW Frequency bandwidth (-1 dB)
DC .. 100
%
%
mA
mA
mA
mA
µs
A/µs
kHz
General data
TA Ambient operating temperature
TS Ambient storage temperature
RS Secondary coil resistance
@ TA = 70°C
@ TA = 85°C
m Mass
Standards
- 40 .. + 85
°C
- 50 .. + 90
°C
25
Ω
26
Ω
1.5
kg
EN 50178: 1997
Features
●● Closed loop (compensated)
current transducer using the Hall
effect
●● Isolated plastic case recognized
according to UL 94-V0.
Advantages
●● Excellent accuracy
●● Very good linearity
●● Low temperature drift
●● Optimized response time
●● Wide frequency bandwidth
●● No insertion losses
●● High immunity to external
interference
●● Current overload capability.
Applications
●● AC variable speed drives and
servo motor drives
●● Static converters for DC motor
drives
●● Battery supplied applications
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Power supplies for welding
applications.
Application Domain
●● Industrial.
Note: 1) With a di/dt of 100 A/µs.
05July2011/version 11
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com