English
Language : 

LAH50-P_06 Datasheet, PDF (1/2 Pages) LEM – Current Transducer
Current Transducer LAH 50-P
For the electronic measurement of currents : DC, AC, pulsed ...,
with a galvanic isolation between the primary circuit
(high power) and the secondary circuit (electronic circuit).
IPN = 50 A
Electrical data
16010
I
Primary nominal r.m.s. current
PN
IP
Primary current, measuring range 1)
RM Measuring resistance @
50
A
0 .. 110
A
TA = 70°C TA = 85°C
RM min RMmax RM min RMmax
with ± 12 V
with ± 15 V
@ I [± A ]
PN
DC
@ IPN [A RMS ] 2)
@ I [± A ]
PN
DC
@ IPN [A RMS ] 2)
0 221 0 214 Ω
0 115 0 108 Ω
0 335 0 327 Ω
0 195 0 188 Ω
ISN
Secondary nominal r.m.s. current
25
mA
K
Conversion ratio
N
1 : 2000
VC
Supply voltage (± 5 %)
± 12 .. 15
V
IC
Current consumption
10 (@ ± 15V) + IS mA
Vd
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn 5
kV
Ve
R.m.s. voltage for partial discharge extinction @ 10 pC > 2
kV
V
Impulse withstand voltage 1.2/50 µs
w
> 12
kV
Accuracy - Dynamic performance data
X
Accuracy 3) @ I T = 25°C
εL
Linearity
PN, A
± 0.25
%
< 0.15
%
Typ Max
I
Offset current @ T = 25°C
O
A
± 0.15 mA
IOM
Residual current @ IP = 0, after an overload of 5 x IPN ± 0.10 ± 0.15 mA
IOT
Thermal drift of IO
0°C .. + 70°C ± 0.10 ± 0.30 mA
- 25°C .. + 85°C ± 0.10 ± 0.40 mA
tr a
tr
di/dt
f
Reaction time @ 10 % of IPN
Response time 4) @ 90 % of IPN
di/dt accurately followed
Frequency bandwidth (- 1 dB)
< 200
< 500
> 200
DC .. 200
ns
ns
A/µ s
kHz
General data
TA
Ambient operating temperature
T
Ambient storage temperature
S
R S Secondary coil resistance
Insulating material group
m
Mass
Standards 5)
- 25 .. + 85
°C
- 40 .. + 90
°C
@ TA = 70°C 135
Ω
@ TA = 85°C 142
Ω
I
22
g
EN 50178
Features
• Closed loop (compensated) current
transducer using the Hall effect
• Printed circuit board mounting
• Insulated plastic case recognized
according to UL 94-V0.
Advantages
• Excellent accuracy
• Very good linearity
• Low temperature drift
• Optimized response time
• Wide frequency bandwidth
• No insertion losses
• High immunity to external
interference
• Current overload capability.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
Notes : 1) For 10 s, with RM ≤ 71 Ω (VC = ± 15 V)
2) 50 Hz Sinusoidal
3) Without I & I
O OM
4) With a di/dt of 100 A/µs
5) A list of corresponding tests is available.
LEM
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
060124/7
page 1/3
w w w .lem.com