IP N = 8-12-25 A
Electrical data
IP N Primary nominal RMS current
IP M Primary current, measuring range 1)
RM Measuring resistance @ 2)
with ±12 V
@ IP N [±At DC]
@ IP N [At RMS] 3)
with ±15 V
@ IP N [±At DC]
@ IP N [At RMS] 3)
@
IP
<
I 4)
PN
IS N Secondary nominal RMS current
KN Conversion ratio
UC Supply voltage (±5 %)
IC
Current consumption
25
0 ⦠±55
TA = 70 °C
R R M min M max
0 284
0 182
67 398
67 263
At
At
TA = 85 °C
R R M min M max
0 280 â¦
0 178 â¦
70 394 â¦
70 259 â¦
25
mA
1-2-3 : 1000
±12 ⦠15
V
10 (@ ±15 V) +IS
mA
Accuracy - Dynamic performance data
X
Accuracy 5) @ IP N, TA = 25 °C
εL
Linearity error
±0.3
%
< 0.2
%
Typ Max
IO
Offset current @ IP = 0, TA = 25 °C
±0.15
mA
IO M Magnetic offset current @ IP = 0,
and specified RM, after an overload of 5 Ã IP N
±0.20 ±0.25
mA
IO T Temperature variation of IO 0 °C ⦠+70 °C
±0.10 ±0.60
mA
â25 °C ⦠+85 °C
±0.10 ±0.70
mA
tra
Reaction time to 10 % of IP N
tr
Step response time 6) to 90 % of IP N
BW Frequency bandwidth (â1 dB)
< 200
ns
< 500
ns
DC ⦠200
kHz
General data
TA Ambient operating temperature
â25 ⦠+85
°C
TS Ambient storage temperature
â40 ⦠+90
°C
RS Resistance of secondary winding @ TA = 70 °C 72
â¦
@ TA = 85 °C 76
â¦
m Mass
20
g
Standards
EN 50178: 1997
Notes: 1) During 10 s, with RM ⤠109 ⦠(UC = ±15 V)
2) Calculation of RM min with the maximum power of the transistors = 0.307 W
@ 70 °C and the maximum power of the transistors = 0.302 W @ 85 °C
3) Sinusoidal wave 50 Hz
4) The minimum measuring resistance RM may be lower
(see âLAH technical informationâ leaflet)
5) Without IO & IO M
6) With a di/dt of 100 A/µs.
Features
ââ Closed loop (compensated) multi-
range current transducer using
the Hall effect
ââ Printed circuit board mounting
ââ Insulating plastic case recognized
according to UL 94-V0.
Advantages
ââ Excellent accuracy
ââ Very good linearity
ââ Low temperature drift
ââ Optimized response time
ââ No insertion losses
ââ High immunity to external
interference
ââ Current overload capability.
Applications
ââ AC variable speed drives and
servo motor drives
ââ Static converters for DC motor
drives
ââ Battery supplied applications
ââ Uninterruptible Power Supplies
(UPS)
ââ Switched Mode Power Supplies
(SMPS)
ââ Power supplies for welding
applications.
Application domain
ââ Industrial.
N° 97.34.19.000.0
24February2017/Version 9
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
Page 1/3