English
Language : 

LA25-SP14_06 Datasheet, PDF (1/2 Pages) LEM – Current Transducer
Current Transducer LA 25-NP/SP14
For the electronic measurement of currents : DC, AC, pulsed,
mixed, with a galvanic isolation between the primary circuit
(high power) and the secondary circuit (electronic circuit).
IPN = 0.25 A
Electrical data
16094
IPN
Primary nominal r.m.s. current
IP
Primary current, measuring range
RM Measuring resistance
with ± 15 V
@ ± 0.25 A
max
@ ± 0.36 A max
ISN
Secondary nominal r.m.s. current
K
Conversion ratio
N
VC Supply voltage (± 5 %)
I
Current consumption
C
Vd
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
V
R.m.s. rated voltage 1), safe separation
b
basic isolation
0.25
A
0 .. ± 0.36
A
RM min
RM max
100 320 Ω
100 190 Ω
25
mA
100 : 1000
± 15
V
10 + I
mA
S
2.5
kV
600
V
1700
V
Accuracy - Dynamic performance data
X
ε
Typical accuracy @ IPN , TA = 25°C
Linearity error
L
± 0.5
%
< 0.2
%
Typ Max
IO
Offset current 2) @ IP = 0, TA = 25°C
± 0.05 ± 0.15 mA
IOM Residual current 3) @ IP = 0, after an overload of 3 x IPN ± 0.05 ± 0.15 mA
IOT
Thermal drift of IO
- 10°C .. + 70°C ± 0.10 ± 0.35 mA
t
Response time 4) @ 90 % of I
r
PN
f
Frequency bandwidth (- 1 dB)
<1
µs
DC .. 150 kHz
General data
TA
Ambient operating temperature
T
Ambient storage temperature
S
R P Primary coil resistance @ TA = 25°C
R
Secondary coil resistance @ T = 70°C
S
A
L P Primary insertion inductance
R
Isolation resistance @ 500 V, T = 25°C
IS
A
m
Mass
Standards
- 10 .. + 70
°C
- 25 .. + 85
°C
< 860
mΩ
110
Ω
496
µH
> 1500
MΩ
22
g
EN 50178 : 1997
Notes : 1) Pollution class 2
2) Measurement carried out after 15 mn functioning
3) The result of the coercive field of the magnetic circuit
4) With a di/dt of 100 A/µs.
Features
• Closed loop (compensated) multi-
turns current transducer using the
Hall effect
• Printed circuit board mounting
• Insulated plastic case recognized
according to UL 94-V0.
Special features
• IPN = 0.25 A
•
I
P
= 0 .. ± 0.36 A
• K N = 100 : 1000
•
T
A
=
- 10°C .. + 70°C.
Advantages
• Excellent accuracy
• Very good linearity
• Low temperature drift
• Optimized response time
• Wide frequency bandwidth
• No insertion losses
• High immunity to external
interference
• Current overload capability.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
060405/4
LEM