Current Transducer LA 25-NP/SP11
For the electronic measurement of currents : DC, AC, pulsed,
mixed, with a galvanic isolation between the primary circuit
(high power) and the secondary circuit (electronic circuit).
IPN = 1 A
Electrical data
IPN
Primary nominal r.m.s. current
IP
Primary current, measuring range
RM Measuring resistance
with ± 15 V
@ ± 1.0 A max
@ ± 1.5 A
max
I
Secondary nominal r.m.s. current
SN
K N Conversion ratio
V
Supply voltage (± 5 %)
C
IC
Current consumption
V
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
d
Vb
R.m.s. rated voltage 1), safe separation
basic isolation
1
A
0 .. ± 1.5
A
RM min
RM max
100 320 Ω
100 190 Ω
25
mA
25 : 1000
± 15
V
10 + IS
mA
2.5
kV
600
V
1700
V
Accuracy - Dynamic performance data
X
Typical accuracy @ I , T = 25°C
εL
Linearity
PN A
± 0.5
%
< 0.2
%
Typ Max
IO
Offset current 2) @ IP = 0, TA = 25°C
± 0.05 ± 0.15 mA
IOM Residual current 3) @ IP = 0, after an overload of 3 x IPN ± 0.05 ± 0.15 mA
IOT
Thermal drift of IO
0°C .. + 25°C ± 0.06 ± 0.25 mA
+ 25°C .. + 70°C ± 0.10 ± 0.35 mA
tr
Response time 4) @ 90 % of IP max
f
Frequency bandwidth (- 1 dB)
<1
µs
DC .. 150 kHz
General data
TA
Ambient operating temperature
T
Ambient storage temperature
S
R P Primary coil resistance @ TA = 25°C
R
Secondary coil resistance @ T = 70°C
S
A
L P Primary insertion inductance
R
Isolation resistance @ 500 V, T = 25°C
IS
A
m
Mass
Standards 5)
0 .. + 70
°C
- 25 .. + 85
°C
< 51
mΩ
110
Ω
31
µH
> 1500
MΩ
22
g
EN 50178
Notes : 1) Pollution class 2
2) Measurement carried out after 15 mn functionning
3) The result of the coercive field of the magnetic circuit
4) With a di/dt of 100 A/µs
5) A list of corresponding tests is available
Features
•Closed loop (compensated) multi-
turns current transducer using the
Hall effect
•Insulated plastic case recognized
according to UL 94-V0.
Special features
•IPN = 1 A
•IP = 0 .. ± 1.5 A
•K N = 25 : 1000.
Advantages
•Excellent accuracy
•Very good linearity
•Low temperature drift
•Optimized response time
•Wide frequency bandwidth
•No insertion losses
•High immunity to external
interference
•Current overload capability.
Applications
•AC variable speed drives and servo
motor drives
•Static converters for DC motor drives
•Battery supplied applications
•Uninterruptible Power Supplies
(UPS)
•Switched Mode Power Supplies
(SMPS)
•Power supplies for welding
applications.