English
Language : 

LA25-NP Datasheet, PDF (1/2 Pages) LEM – Current Transducer LA 25-NP
Current Transducer LA 25-NP
For the electronic measurement of currents : DC, AC, pulsed,
mixed, with a galvanic isolation between the primary circuit
(high power) and the secondary circuit (electronic circuit).
IPN = 5-6-8-12-25 A
Electrical data
IPN
Primary nominal r.m.s. current
I
Primary current, measuring range
P
RM Measuring resistance
with ± 15 V
@ ± 25 At max
@ ± 36 At
max
ISN
Secondary nominal r.m.s. current
K N Conversion ratio
VC Supply voltage (± 5 %)
IC
Current consumption
Vd
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
Vb
R.m.s. rated voltage 1), safe separation
basic isolation
25
At
0 .. ± 36
At
RM min
RM max
100 320 Ω
100 190 Ω
25
mA
1-2-3-4-5 : 1000
± 15
V
10 + IS
mA
2.5
kV
600
V
1700
V
Accuracy - Dynamic performance data
X
εL
Accuracy @ IPN , TA = 25°C
Linearity
± 0.5
%
< 0.2
%
Typ Max
I
Offset current 2) @ I = 0, T = 25°C
O
P
A
± 0.05 ± 0.15 mA
IOM
Residual current 3) @ IP = 0, after an overload of 3 x IPN ± 0.05 ± 0.15 mA
I
Thermal drift of I
OT
O
0°C .. + 25°C ± 0.06 ± 0.25 mA
+ 25°C .. + 70°C ± 0.10 ± 0.35 mA
tr
di/dt
f
Response time 4) @ 90 % of IP max
di/dt accurately followed
Frequency bandwidth (- 1 dB)
<1
> 50
DC .. 150
µs
A/µs
kHz
General data
T
Ambient operating temperature
A
TS
Ambient storage temperature
R
Primary resistance per turn @ T = 25°C
P
A
R S Secondary coil resistance @ TA = 70°C
R IS Isolation resistance @ 500 V, TA = 25°C
m
Mass
Standards 5)
0 .. + 70
°C
- 25 .. + 85
°C
< 1.25
mΩ
110
Ω
> 1500
MΩ
22
g
EN 50178
Features
•Closed loop (compensated) multi-
range current transducer using the
Hall effect
•Insulated plastic case recognized
according to UL 94-V0.
Advantages
•Excellent accuracy
•Very good linearity
•Low temperature drift
•Optimized response time
•Wide frequency bandwidth
•No insertion losses
•High immunity to external
interference
•Current overload capability.
Applications
•AC variable speed drives and servo
motor drives
•Static converters for DC motor drives
•Battery supplied applications
•Uninterruptible Power Supplies
(UPS)
•Switched Mode Power Supplies
(SMPS)
•Power supplies for welding
applications.
Notes : 1) Pollution class 2
2) Measurement carried out after 15 mn functionning
3) The result of the coercive field of the magnetic circuit
4) With a di/dt of 100 A/µs
5) A list of corresponding tests is available
LEM Components
980909/8
w w w .lem.com