LA205-S_11 Datasheet, PDF (1/3 Pages) LEM – Current Transducer | |||
|
Current Transducer LA 205-S
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 200 A
16137
Electrical data
IPN
Primary nominal current rms
IPM
Primary current, measuring range
îP max Measuring overload 1)
RM
Measuring resistance
with ± 12 V
@ ± 200 A max
@ ± 300 A max
with ± 15 V
@ ± 200 A max
@ ± 300 A max
ISN
Secondary nominal current rms
KN
Conversion ratio
VC
Supply voltage (± 5 %)
IC
Current consumption
Accuracy - Dynamic performance data
200
A
0 .. ± 300
A
600
A
TA = 70°C TA = 85°C
R R R R M min M max M min M max
0 68 0 66 â¦
0 33 0 30 â¦
5 95 5 93 â¦
5 50 5 49 â¦
100
mA
1 : 2000
± 12 .. 15
V
20 (@ ± 15 V) + IS mA
XεG
L
IO
IOM
IOT
tra
tr
di/dt
BW
Overall accuracy @ IPN , TA = 25°C
Linearity error
± 0.8
< 0.1
Typ Max
Offset current @ IP = 0, TA = 25°C
± 0.15
Magnetic offset current 2) @ IP = 0 and specified RM,
after an overload of 3 x IPN
± 0.50
Temperature variation of IO
- 10°C .. + 85°C ± 0.15 ± 0.30
Reaction time @ 10 % of IPN
< 500
Response time 3) @ 90 % of IPN step
< 1
di/dt accurately followed
> 100
Frequency bandwidth (- 3 dB)
DC .. 100
%
%
mA
mA
mA
mA
ns
µs
A/µs
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
RS
Secondary coil resistance
@ TA = 70°C
@ TA = 85°C
m
Mass
Standards
- 10 .. + 85
°C
- 40 .. + 90
°C
35
â¦
37
â¦
110
g
EN 50178: 1997
Notes: 1) 3 mn/hour @ VC = ± 15 V, RM = 5 â¦
2) The result of the coercive force (Hc) of the magnetic circuit
3) With a di/dt of 100 A/µs.
Features
ââ Closed loop (compensated)
current transducer using the Hall
effect
ââ Isolated plastic case recognized
according to UL 94-V0
ââ Patent pending.
Advantages
ââ Excellent accuracy
ââ Very good linearity
ââ Low temperature drift
ââ Optimized response time
ââ Wide frequency bandwidth
ââ No insertion losses
ââ High immunity to external
interference
ââ Current overload capability.
Applications
ââ AC variable speed drives and
servo motor drives
ââ Static converters for DC motor
drives
ââ Battery supplied applications
ââ Uninterruptible Power Supplies
(UPS)
ââ Switched Mode Power Supplies
(SMPS)
ââ Power supplies for welding
applications.
Application domain
ââ Industrial.
110126/9
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com
|
▷ |