LA205-S Datasheet, PDF (1/2 Pages) LEM – Current Transducer LA 205-S | |||
|
Current Transducer LA 205-S
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 200 A
Electrical data
IPN
I
P
ÃP max
R
M
Primary nominal r.m.s. current
Primary current, measuring range
Measuring overload 1)
Measuring resistance @
with ± 12 V
with ± 15 V
@ ± 200 A max
@ ± 300 A
max
@ ± 200 A max
@ ± 300 A
max
ISN
Secondary nominal r.m.s. current
K N Conversion ratio
VC Supply voltage (± 5 %)
IC
Current consumption
Vb
R.m.s rated voltage 2), safe separation
basic isolation
200
A
0 .. ± 300
A
600
A
T = 70°C T = 85°C
A
A
R R R R M min M max M min M max
0 68 0 66 â¦
0 33 0 30 â¦
5 95 5 93 â¦
5 50 5 49 â¦
100
mA
1 : 2000
± 12 .. 15
V
20 (@ ± 15 V) + IS mA
1625
V
3250
V
Accuracy - Dynamic performance data
X
εG
L
IO
I
OM
IOT
tra
t
r
di/dt
f
Overall accuracy @ I , T = 25°C
PN A
Linearity
± 0.8
%
< 0.1
%
Typ Max
Offset current @ IP = 0, TA = 25°C
± 0.15 mA
Residual current 3) @ I = 0, after an overload of 3 x I
P
PN
± 0.50 mA
Thermal drift of IO
- 10°C .. + 85°C ± 0.15 ± 0.30 mA
Reaction time @ 10 % of IP max
Response time 4) @ 90 % of I
P max
di/dt accurately followed
< 500
<1
> 100
ns
µs
A/µs
Frequency bandwidth (- 3 dB)
DC .. 100
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
R S Secondary coil resistance @
m
Mass
- 10 .. + 85
°C
- 40 .. + 90
°C
TA = 70°C 35
â¦
TA = 85°C 37
â¦
110
g
Standards 5)
EN 50178
Notes : 1) 3 mn/hour @ VC = ± 15 V, R M = 5 â¦
2) Pollution class nr 2. With a non insulated primary bar which fills the
through-hole
3) The result of the coercive field of the magnetic circuit
4) With a di/dt of 100 A/µs
5) A list of corresponding tests is available
Features
â¢Closed loop (compensated) current
transducer using the Hall effect
â¢Insulated plastic case recognized
according to UL 94-V0
â¢Patent pending.
Advantages
â¢Excellent accuracy
â¢Very good linearity
â¢Low temperature drift
â¢Optimized response time
â¢Wide frequency bandwidth
â¢No insertion losses
â¢High immunity to external
interference
â¢Current overload capability.
Applications
â¢AC variable speed drives and servo
motor drives
â¢Static converters for DC motor drives
â¢Battery supplied applications
â¢Uninterruptible Power Supplies
(UPS)
â¢Switched Mode Power Supplies
(SMPS)
â¢Power supplies for welding
applications.
980716/5
LEM Components
w w w .lem.com
|
▷ |