LA200-P_09 Datasheet, PDF (1/3 Pages) LEM – Current Transducer | |||
|
Current Transducer LA 200-P
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 200 A
16044
Electrical data
IPN
Primary nominal current rms
200
A
IPM Primary current, measuring range 0 .. ± 300
A
RM Measuring resistance @
TA = 70°C TA = 85°C
R R R R M min M max
M min M max
with ± 12 V
@ ± 200 A max
0 30 0 26 â¦
@ ± 250 A max
0
80
4
â¦
with ± 15 V
@ ± 200 A max
0 60 0 56 â¦
@ ± 300 A max
0 12 0
8
â¦
ISN
Secondary nominal current rms
100
mA
KN Conversion ratio 1 : 2000
VC Supply voltage (± 5 %) ± 12 .. 15
V
IC
Current consumption 16 (@ ± 15 V) + IS mA
Accuracy - Dynamic performance data
X
Accuracy @ IPN , TA = 25°C @ ± 15 V (± 5 %)
± 0.40
@ ± 12 .. 15 V (± 5 %) ± 0.65
ε
L
Linearity error < 0.15
Typ Max
IO
Offset current @ IP = 0, TA = 25°C
± 0.20
IOM
Magnetic offset current 1) @ IP = 0 and specified RM,
after an overload of 3 x IPN
± 0.25
IOT
Temperature variation of IO
0°C .. + 70°C ± 0.10 ± 0.25
- 40°C .. + 85°C ± 0.15 ± 0.55
tra
tr
di/dt
Reaction time to 10 % of IPN step
Response time 2) 3) to 90 % of IPN step
di/dt accurately followed 3)
< 500
< 1
> 200
BW Frequency bandwidth (- 1 dB) DC .. 100
%
%
%
mA
mA
mA
mA
ns
µs
A/µs
kHz
General data
TA
Ambient operating temperature - 40 .. + 85
°C
TS
Ambient storage temperature - 40 .. + 90
°C
RS Secondary coil resistance @
TA = 70°C
76
â¦
TA = 85°C
80
â¦
m
Mass 40
g
Standards EN 50178: 1997
Features
ââ Closed loop (compensated)
current transducer using the Hall
effect
ââ Printed circuit board mounting
ââ Isolated plastic case recognized
according to UL 94-V0.
Advantages
ââ Excellent accuracy
ââ Very good linearity
ââ Low temperature drift
ââ Optimized response time
ââ Wide frequency bandwidth
ââ No insertion losses
ââ High immunity to external
interference
ââ Current overload capability.
Applications
ââ AC variable speed drives and
servo motor drives
ââ Static converters for DC motor
drives
ââ Battery supplied applications
ââ Uninterruptible Power Supplies
(UPS)
ââ Switched Mode Power Supplies
(SMPS)
ââ Power supplies for welding
applications.
Application domain
ââ Industrial.
Notes: 1) The result of the coercive field of the magnetic circuit
2) With a di/dt of 100 A/µs
3) The primary conductor is best filling the through-hole and/or the return of
the primary conductor is above the top of the transducer.
090508/15
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com
|
▷ |