English
Language : 

LA200-P_06 Datasheet, PDF (1/2 Pages) LEM – Current Transducer
Current Transducer LA 200-P
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 200 A
16044
Electrical data
I
Primary nominal r.m.s. current
PN
IP
Primary current, measuring range
R
Measuring resistance @
M
with ± 12 V
with ± 15 V
@ ± 200 A
max
@ ± 250 A max
@ ± 200 A
max
@ ± 300 A max
200
A
0 .. ± 300
A
T = 70°C T = 85°C
A
A
R R R R M min M max M min M max
0 30 0 26 Ω
08 04 Ω
0 60 0 56 Ω
0 12 0 8 Ω
Features
• Closed loop (compensated) current
transducer using the Hall effect
• Printed circuit board mounting
• Insulated plastic case recognized
according to UL 94-V0.
I SN Secondary nominal r.m.s. current
100
mA Advantages
K
Conversion ratio
N
1 : 2000
VC Supply voltage (± 5 %)
± 12 .. 15
V • Excellent accuracy
I
Current consumption
C
16
(@
±
15
V
)
+
I
S
mA
• Very good linearity
Vd
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
3
kV • Low temperature drift
V
R.m.s. rated voltage, 1)
b
safe separation 900
V • Optimized response time
basic isolation 450
V • Wide frequency bandwidth
Ve
R.m.s. voltage for partial discharge extinction
VW Impulse withstand voltage 1.2/50 µs
Accuracy - Dynamic performance data
> 1.8
>8
kV • No insertion losses
kV • High immunity to external
interference
• Current overload capability.
X
Accuracy @ IPN , TA = 25°C
@ ± 15 V (± 5 %) ± 0.40
%
@ ± 12 .. 15 V (± 5 %) ± 0.65
%
εL
Linearity error
< 0.15
%
Typ Max
IO
Offset current @ IP = 0, TA = 25°C
± 0.20 mA
IOM Residual current 2) @ IP = 0, after an overload of 3 x IPN
± 0.25 mA
I OT Thermal drift of IO
0°C .. + 70°C ± 0.10 ± 0.25 mA
- 40°C .. + 85°C ± 0.15 ± 0.55 mA
t ra
t
r
di/dt
f
Reaction time @ 10 % of IP max
Response time 3) 4) @ 90 % of I
P max
di/dt accurately followed 4)
Frequency bandwidth 4) (- 1 dB)
< 500
<1
> 200
DC .. 100
ns
µs
A/µs
kHz
General data
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
TA
Ambient operating temperature
T
Ambient storage temperature
S
R S Secondary coil resistance @
m
Mass
TA = 70°C
T = 85°C
A
- 40 .. + 85
- 40 .. + 90
76
80
40
°C Application Domain
°C
Ω • Industrial.
Ω
g
Standards
EN 50178 : 1997
Notes : 1) Pollution class 2 2) The result of the coercive field of the magnetic circuit
3) With a di/dt of 100 A/µs 4)The primary conductor is best filling
the through-hole and/or the return of the primary conductor is above
the top of the transducer.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
060303/12
Page 1/2
LEM
www.lem.com