English
Language : 

LA150-TP Datasheet, PDF (1/3 Pages) LEM – Current Transducer
Current Transducer LA 150-TP
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit and the secondary
circuit.
IPN = 150 A
Electrical data
IPN
Primary nominal current rms
IPM
Primary current, measuring range
RM
Measuring resistance @ 85°C
with ± 12 V
@ ± 150 A max
@ ± 212 A max
with ± 15 V
@ ± 150 A max
@ ± 212 A max
ISN
Secondary nominal current rms
KN
Conversion ratio
VC
Supply voltage (± 5 %)
IC
Current consumption
Accuracy - Dynamic performance data
150
A
0 .. ± 212
A
R R M min
M max
0
40
Ω
0
3
Ω
0
78
Ω
0
30
Ω
75
mA
1 : 2000
± 12 .. 15
V
10 (@ ± 15 V) + Is mA
X
ε
L
IOE
IOM
IOT
tra
tr
di/dt
BW
Accuracy @ IPN, TA = 25°C
Linearity error
< 0.5
< 0.1
Typ Max
Electrical offset current @ IP = 0, TA = 25°C
± 0.10
Magnetic offset current @ IP = 0 and specified RM,
after an overload of 3 x IPN
± 0.25
Temperature variation of IO
- 40°C .. + 85°C ± 0.15 ± 0.30
Reaction time to 10 % of IPN step
< 300
Response time 1) to 90 % of IPN step
< 500
di/dt accurately followed
> 100
Frequency bandwidth (- 1 dB)
DC .. 150
%
%
mA
mA
mA
ns
ns
A/µs
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
RS
Secondary coil resistance @ TA = 25°C
m
Mass
Standard
- 40 .. + 85
°C
- 40 .. + 90
°C
64 ± 2
Ω
< 35
g
EN 50178: 1997
Features
●● Closed loop (compensated)
current transducer using the Hall
effect
●● Isolated plastic case recognized
according to UL 94-V0.
Advantages
●● Excellent accuracy
●● Very good linearity
●● Low temperature drift
●● Optimized response time
●● Wide frequency bandwidth
●● No insertion losses
●● High immunity to external
interference
●● Current overload capability.
Applications
●● AC variable speed drives and
servo motor drives
●● Static converters for DC motor
drives
●● Battery supplied applications
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Power supplies for welding
applications.
Application domain
●● Industrial.
Note: 1) With a di/dt of 100 A/µs.
14December2012/version 3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
Page 1/3
www.lem.com