LA100-P_09 Datasheet, PDF (1/3 Pages) LEM – Current Transducer | |||
|
Current Transducer LA 100-P
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 100 A
16019
Electrical data
IPN
Primary nominal current rms
100
A
IPM Primary current, measuring range 0 .. ± 150
A
RM Measuring resistance @
TA = 70°C TA = 85°C
R R R R M min M max
M min M max
with ± 12 V
@ ± 100 A max
0 50 0 42 â¦
@ ± 120 A max
0 22 0 14 â¦
with ± 15 V
@ ± 100 A max
0 110 20 102 â¦
@ ± 150 A max
0 33 20 25 â¦
ISN
Secondary nominal current rms
50
mA
KN Conversion ratio 1 : 2000
VC Supply voltage (± 5 %) ± 12 .. 15
V
IC
Current consumption 10 (@ ± 15 V) + IS mA
Accuracy - Dynamic performance data
X
ε
L
IO
IOM
IOT
tra
tr
di/dt
BW
Accuracy @ IPN , TA = 25°C @ ± 15 V (± 5 %)
@ ± 12 .. 15 V (± 5 %)
± 0.45
± 0.70
Linearity error < 0.15
Typ Max
Offset current @ IP = 0, TA = 25°C
± 0.10
Magnetic offset current 1) @ IP = 0 and specified RM,
after an overload of 3 x IPN
± 0.15
Temperature variation of IO
- 25°C .. + 85°C ± 0.05 ± 0.30
- 40°C .. - 25°C ± 0.10 ± 0.50
Reaction time to 10 % of IPN step
Response time 2) to 90 % of IPN step
di/dt accurately followed
< 500
< 1
> 200
Frequency bandwidth (- 1 dB) DC .. 200
%
%
%
mA
mA
mA
mA
ns
µs
A/µs
kHz
General data
TA
Ambient operating temperature - 40 .. + 85
°C
TS
Ambient storage temperature - 40 .. + 90
°C
RS Secondary coil resistance
@ TA = 70°C
120
â¦
@ TA = 85°C
128
â¦
m
Mass 18
g
Standards 3) EN 50178: 1997
Features
ââ Closed loop (compensated)
current transducer using the Hall
effect
ââ Printed circuit board mounting
ââ Insulated plastic case recognized
according to UL 94-V0.
Advantages
ââ Excellent accuracy
ââ Very good linearity
ââ Low temperature drift
ââ Optimized response time
ââ Wide frequency bandwidth
ââ No insertion losses
ââ High immunity to external
interference
ââ Current overload capability.
Applications
ââ AC variable speed drives and
servo motor drives
ââ Static converters for DC motor
drives
ââ Battery supplied applications
ââ Uninterruptible Power Supplies
(UPS)
ââ Switched Mode Power Supplies
(SMPS)
ââ Power supplies for welding
applications.
Application domain
ââ Industrial.
Notes: 1) Result of the coercive field of the magnetic circuit
2) With a di/dt of 100 A/µs
3) A list of corresponding tests is available.
090615/10
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com
|
▷ |