LA-100-P Datasheet, PDF (1/3 Pages) LEM – Current Transducer LA 100-P | |||
|
Current Transducer LA 100-P
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic separation between the primary circuit and the secondary
circuit.
IPN = 100 A
Electrical data
IPN Primary nominal rms current 100
A
IPM Primary current, measuring range 0 ... ±150
A
RM Measuring resistance @
TA = 70 °C TA = 85 °C
R R R R M min M max
M min M max
with ±12 V
@ ±100 A max
0 50 0 42 â¦
@ ±120 A max
0 22 0 14 â¦
with ±15 V
@ ±100 A max
0 110 20 102 â¦
@ ±150 A max
0 33 20 25 â¦
ISN Secondary nominal rms current 50
mA
KN Conversion ratio 1 : 2000
UC Supply voltage (±5 %) ±12 ⦠15
V
IC
Current consumption 10 (@ ±15 V) + IS mA
Accuracy - Dynamic performance data
X
Accuracy @ IPN, TA = 25 °C @ ±15 V (±5 %) ±0.45
%
@ ±12 ⦠15 V (±5 %) ±0.70
%
εL
Linearity error < 0.15
%
Typ Max
IO
Offset current @ IP = 0, TA = 25 °C
±0.10 mA
IOM Magnetic offset current 1) @ IP = 0 and specified RM,
after an overload of 3 Ã IPN
±0.15 mA
IOT Temperature variation of IO â25 °C ⦠+85 °C
±0.05 ±0.30 mA
â40 °C ⦠â25 °C ±0.10 ±0.50 mA
tra
Reaction time
tr
Step response time 2) to 90 % of IPN
di/dt di/dt accurately followed
< 500
< 1
> 200
ns
µs
A/µs
BW Frequency bandwidth (â1 dB) DC ⦠200
kHz
General data
TA
Ambient operating temperature â40 ⦠+85
°C
TS
Ambient storage temperature â40 ⦠+90
°C
RS
Resistance of secondary winding @ TA = 70 °C
120
â¦
@ TA = 85 °C
128
â¦
m
Mass 18
g
Standards EN 50178: 1997
UL 508: 2010
Notes: 1) Result of the coercive field of the magnetic circuit
2) With a di/dt of 100 A/µs.
Features
ââ Closed loop (compensated)
current transducer using the Hall
effect
ââ Insulated plastic case recognized
according to UL 94-V0.
Advantages
ââ Excellent accuracy
ââ Very good linearity
ââ Low temperature drift
ââ Optimized response time
ââ Wide frequency bandwidth
ââ No insertion losses
ââ High immunity to external
interference
ââ Current overload capability.
Applications
ââ AC variable speed drives and
servo motor drives
ââ Static converters for DC motor
drives
ââ Battery supplied applications
ââ Uninterruptible Power Supplies
(UPS)
ââ Switched Mode Power Supplies
(SMPS)
ââ Power supplies for welding
applications.
Application domain
ââ Industrial.
N° 97.09.34.000.0
27January2016/version 12
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
Page 1/3
www.lem.com
|
▷ |