HXS50-SP2 Datasheet, PDF (1/3 Pages) LEM – Current Transducer | |||
|
Current Transducer HXS 50-NP/SP2
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 12.5 - 25 - 50 A
Electrical data
All Data are given with a RL = 10 kâ¦
IPN
I
P
VOUT
VREF
R
L
ROUT
C
L
VC
I
C
Primary nominal r.m.s. current
Primary current measuring range
Analog output voltage @ IP
I =0
P
Internal Reference 1) - Output voltage
V Output impedance
REF
VREF Load impedance
Output load resistance
Output impedance
Max. output capacitive load
Supply voltage (± 5 %)
Current consumption @ V = 5 V
C
± 50
A
± 150
A
VREF ±(0.625·IP/IPN) V
V ± 0.0125 V
REF
2.5 ± 0.025
V
typ. 200
â¦
⥠200
kâ¦
â¥2
kâ¦
< 10
â¦
<1
µF
5
V
22
mA
Features
⢠Hall effect measuring principle
⢠Multirange current transducer
through PCB pattern lay-out
⢠Galvanic isolation between primary
and secondary circuit
⢠Isolation test voltage 3500V
⢠Low power consumption
⢠Extremely low profile, < 11mm
⢠Single power supply +5V
⢠Fixed offset & gain
⢠Insulated plastic case recognized
according to UL 94-V0.
Accuracy - Dynamic performance data
X
εL
Accuracy 2) @ IPN , TA = 25°C
Linearity error 0 .. IPN
â¤Â±1
⤠± 0.5
% of IPN
% of IPN
.. 3 x IPN
â¤Â±1
% of IPN
TCVOUT Thermal drift of VOUT @ IP = 0
⤠± 0.4
mV/K
TCVREF Thermal drift of VREF
⤠± 0.01
%/K
ε TCVOUT / VREF Thermal drift of VOUT / VREF @ IP = 0
TC Thermal drift of the gain
G
⤠± 0.2
mV/K
⤠± 0.05% of reading/K
VOM Residual voltage @ IP = 0, after an overload of 3 x IPN DC < ± 1
% of IPN
t
Reaction time @ 10 % of I
ra
PN
<3
µs
tr
Response time @ 90 % of IPN
<5
µs
di/dt di/dt accurately followed
> 50
A/µs
Vno Output noise (DC ..10 kHz)
(DC .. 1 MHz)
< 20
< 40
mVpp
mVpp
f
Frequency bandwidth (-3 dB) 3)
DC .. 50
kHz
Special Feature
⢠TA = -40 .. +105 °C
Advantages
⢠Small size and space saving
⢠Only one design for wide current
ratings range
⢠High immunity to external
interference.
⢠Internal & external reference
Applications
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
m
Mass
Standards
- 40 .. + 105 °C
- 40 .. + 105 °C
10
g
EN 50178 (97-10-01)
⢠AC variable speed drives
⢠Static converters for DC motor drives
⢠Battery supplied applications
⢠Uninterruptible Power Supplies
(UPS)
⢠Switched Mode Power Supplies
(SMPS)
⢠Power supplies for welding
applications.
Notes : 1) It is possible to overdrive VREF with an external reference voltage
between 2 - 2.8 V providing its ability to sink or source approximately
2.5 mA.
2) Excluding offset and hysteresis.
3) Small signal only to avoid excessive heatings of the magnetic core.
Application Domain
⢠Industrial
061004/10
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com
|
▷ |