English
Language : 

HX03-P_11 Datasheet, PDF (1/3 Pages) LEM – Current Transducer
Current Transducer HX 03..50-P
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 3 .. 50 A
Electrical data
Primary nominal
current rms
IPN (A)
Primary current
measuring range
IPM (A)
3
±9
5
± 15
10
± 30
15
± 45
20
± 60
25
± 75
50
± 150
All data are given with RL = 10 kW
Primary conductor
Type
diameter x turns
(mm)
0.6d x 20T
0.8d x 12T
1.1d x 6T
1.4d x 4T
1.6d x 3T
1.6d x 2T
1.2 x 6.3 x 1T
HX 03-P
HX 05-P
HX 10-P
HX 15-P
HX 20-P
HX 25-P
HX 50-P
VOUT
ROUT
RL
VC
VC
Output voltage (Anarog) @ ± IPN, RL = 10 kW, TA = 25 °C
Output internal resistance
Load resistance
Supply voltage (± 5 %) 1)
Current consumption
Accuracy - Dynamic performance data
±4
V
< 50
W
≥ 10
kW
± 15
V
< ± 15 mA
X
ε
L
Accuracy @ IPN , TA = 25°C (xcluding offset)
Linearity error (0 .. ± IPN)
< ± 1 % of IPN
< ± 1 % of IPN
VOE Electorical offset voltage @ IP = 0, TA = 25°C
< ± 40 mV
VOH Hysteresis offset voltage @ IP = 0
after an excursion of 1 x IPN
< ± 15 mV
TCVOE Temperature coefficient of VOE
< ± 1.5 mV/K
TCVOUT Temerature coefficient of VOUT (% of reading)
± 0.1 %/K
tr
Response time to 90% of IPN step
≤3
µs
BW Frequency bandwidth (- 3 dB) 2)
50
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
m
Mass
...
Standards
- 25 .. + 85
°C
- 25 .. + 85
°C
8
g
EN 50178: 1997
Note: 1) Also operate at ±12V power supples, measuring range reduced to ± 2.5 x IPN.
2) Small signal only to avoid excssive heating of the magnetic cores.
Features
●● Galvanic isolation between
primary and secondary circuit
●● Hall effect measuring principle
●● Isolation voltage 3000V
●● Low power consumption
●● Extended measuring range (3 x
IPN)
●● Power supply from ±12V to ±15V
●● Isolated plastic case recognized
according to UL 94-V0.
Advantages
●● Low insertion losses
●● Easy to mount with automatic
handling system
●● Small size and space saving
●● Only one design for wide current
ratings range
●● High immunity to external
interference
Applications
●● AC variable speed drives
●● DC motor drives
●● Battery supplied applications
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Electrical appliances
Application domain
●● Industrial
110523/14 .
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com