English
Language : 

HTB50-P_12 Datasheet, PDF (1/3 Pages) LEM – Current Transducer
Current Transducer HTB 50 .. 400 - P
and HTB 50 .. 100 - TP
For the electronic measurement of currents: DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 50 .. 400 A
Electrical data
Primary nominal
current rms
IPN (A)
Primary current
measuring range
IPM (A)
Type
± 50
± 100
± 150
± 200
± 300
± 400
± 150
± 300
± 450
± 500
± 600
± 600
HTB 50-P, HTB 50-TP1)
HTB 100-P, HTB 100-TP1)
HTB 150-P
HTB 200-P
HTB 300-P
HTB 400-P
VC
Supply voltage (± 5 %) 2)
± 12 ..15
V
IC
Current consumption
± 15
mA
Vd
Rms voltage for AC isolation test, 50 Hz, 1 min
2.5
kV
RIS Isolation resistance @ 500 VDC
> 500
MW
VOUT Output voltage (Analog)@ ± IPN, RL = 10kW, TA = 25°C ± 4
V
ROUT Output internal resistance
100
W
RL
Load resistance
> 10
kW
Accuracy - Dynamic performance data
X
e
L
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (0 .. ± IPN)
VOE Electrical offset voltage @ TA = 25°C
VOH Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x IPN
TCVOE Temperature coefficient of VOE HTB 50-(T)P
HTB 100-(T)P .. 400-P
TCVOUT Temperature coefficient of VOUT (% of reading)
tr
Response time to 90% of IPN step
BW Frequency bandwidth (- 3 dB) 3)
< ± 1
< ± 1
< ± 30
< ± 1
< ± 2.0
< ± 1.0
< ± 0.1
< 3
DC .. 50
% of IPN
% of IPN
mV
% of IPN
mV/K
mV/K
%/K
µs
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
m
Mass
Standards
- 40 .. + 80
- 40 .. + 85
< 30 ( < 36)
EN 50178 :
°C
°C
g
1997
2 pins of Ø2mm diameter are available on transducer
for PCB soldering
Notes : 1) -TP version is equipped with a primary bus bar.
2) Operating at ±12V ≤ Vc < ±15V will reduce the measuring range.
3) Derating is needed to avoid excessive core heating at high frequency.
Features
●● Hall effect measuring principle
●● Galvanic isolation between
primary and secondary circuit
●● Isolation voltage 2500 V
●● Low power consumption
●● Wide power supply: ± 12 ..15 V
●● Primary bus bar option for 50
A and 100 A version for ease of
connection
Advantages
●● Small size and space saving
●● Only one design for wide current
ratings range
●● High immunity to external
interference.
Applications
●● AC variable speed drives
●● Static converters for DC motor
drives
●● Battery supplied applications
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Power supplies for welding
applications
Application domain
●● Industrial
120425/12
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com