HTB-200-P Datasheet, PDF (1/3 Pages) LEM – Current Transducer HTB 50 .. 400 - P and HTB 50 .. 100 - TP | |||
|
Current Transducer HTB 50 .. 400 - P
and HTB 50 .. 100 - TP
For the electronic measurement of currents: DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 50 .. 400 A
Electrical data
Primary nominal
current rms
IPN (A)
Primary current
measuring range
IPM (A)
Type
± 50
± 100
± 150
± 200
± 300
± 400
± 150
± 300
± 450
± 500
± 600
± 600
HTB 50-P, HTB 50-TP1)
HTB 100-P, HTB 100-TP1)
HTB 150-P
HTB 200-P
HTB 300-P
HTB 400-P
VC
Supply voltage (± 5 %) 2)
± 12 ..15
V
IC
Current consumption
± 15
mA
Vd
Rms voltage for AC isolation test, 50 Hz, 1 min
2.5
kV
RIS Isolation resistance @ 500 VDC
> 500
MW
VOUT Output voltage (Analog)@ ± IPN, RL = 10kW, TA = 25°C ± 4
V
ROUT Output internal resistance
100
W
RL
Load resistance
> 10
kW
Accuracy - Dynamic performance data
X
e
L
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (0 .. ± IPN)
VOE Electrical offset voltage @ TA = 25°C
VOH Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x IPN
TCVOE Temperature coefficient of VOE HTB 50-(T)P
HTB 100-(T)P .. 400-P
TCVOUT Temperature coefficient of VOUT (% of reading)
tr
Response time to 90% of IPN step
BW Frequency bandwidth (- 3 dB) 3)
< ± 1
< ± 1
< ± 30
< ± 1
< ± 2.0
< ± 1.0
< ± 0.1
< 3
DC .. 50
% of IPN
% of IPN
mV
% of IPN
mV/K
mV/K
%/K
µs
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
m
Mass
Standards
- 40 .. + 80
- 40 .. + 85
< 30 ( < 36)
EN 50178 :
°C
°C
g
1997
2 pins of Ã2mm diameter are available on transducer
for PCB soldering
Notes : 1) -TP version is equipped with a primary bus bar.
2) Operating at ±12V ⤠Vc < ±15V will reduce the measuring range.
3) Derating is needed to avoid excessive core heating at high frequency.
Features
ââ Hall effect measuring principle
ââ Galvanic isolation between
primary and secondary circuit
ââ Isolation voltage 2500 V
ââ Low power consumption
ââ Wide power supply: ± 12 ..15 V
ââ Primary bus bar option for 50
A and 100 A version for ease of
connection
Advantages
ââ Small size and space saving
ââ Only one design for wide current
ratings range
ââ High immunity to external
interference.
Applications
ââ AC variable speed drives
ââ Static converters for DC motor
drives
ââ Battery supplied applications
ââ Uninterruptible Power Supplies
(UPS)
ââ Switched Mode Power Supplies
(SMPS)
ââ Power supplies for welding
applications
Application domain
ââ Industrial
120425/12
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3