English
Language : 

HAX500-S Datasheet, PDF (1/2 Pages) LEM – Current Transducers HAX 500 to 2500-S
Current Transducers HAX 500 to 2500-S
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 500 .. 2500 A
VOUT = ± 4 V
Electrical data
Primary nominal
r.m.s. current
IPN (A)
500
850
1000
1200
1500
2000
2500
Primary current
measuring range
IP (A)
± 1500
± 2550
± 3000
± 3600
± 4500
± 5500
± 5500
Type
HAX 500-S
HAX 850-S
HAX 1000-S
HAX 1200-S
HAX 1500-S
HAX 2000-S
HAX 2500-S
V
C
IC
IOC
V
d
Vb
RIS
VOUT
ROUT
R
L
Supply voltage (± 5 %)
± 15
V
Current consumption
± 15
mA
Overload capacity
30,000
At
R.m.s. voltage for AC isolation test, 60 Hz, 1 mn 5
kV
R.m.s. rated voltage, safe separation
5001)
V
Isolation resistance @ 500 VDC
> 1000 MΩ
Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C
± 4V ± 40 mV
Output internal resistance
approx. 100
Ω
Load resistance
>1
kΩ
Accuracy - Dynamic performance data
X
εL
VOE
V
OH
ε VOT
TC
G
tr
di/dt
f
Accuracy @ I , T = 25°C (without offset)
PN A
Linearity 2) (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ I = 0;
P
after an excursion of 1 x IPN
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
di/dt accurately followed
Frequency bandwidth 3)(- 3 dB)
<±1
%
< ± 1 % of IPN
< ± 20
mV
< ± 30
mV
< ± 1 mV/K
< ± 0.1 %/K
<5
µs
> 50
A/µs
DC .. 25 kHz
General data
TA
Ambient operating temperature
T
Ambient storage temperature
S
m
Mass
- 25 .. + 85 °C
- 25 .. + 85 °C
approx. 450
g
Min. internal creepage distance/clearance
≥ 8.5
mm
Isolation material group
IIIa
Standards 4)
EN 50178
Notes : 1) Pollution class 2, overvoltage category III
2) Linearity data exclude the electrical offset.
3) Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency
4) Please consult characterisation report for more technical details and
application advice.
Features
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Isolation voltage 5000 V~
• Low power consumption
• Extended measuring range (3 x IPN)
• Package in PBT meets UL 94-V0
Advantages
• Easy mounting
• Small size and space savings
• Only one design for wide current
ratings range
• High immunity against external
interference
Applications
• AC motor speed control
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Power supplies for welding, cable TV
and telecommunication applications.
031219/7
LEM Components
www.lem.com