English
Language : 

HAS50-S_06 Datasheet, PDF (1/2 Pages) LEM – Current Transducer
Current Transducer HAS 50 .. 600-S
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 50 .. 600 A
VOUT = ± 4 V
Electrical data
Primary nominal
current rms
IPN (A)
50
100
200
300
400
500
600
Primary current,
measuring range 5)
IPM (A)
± 150
± 300
± 600
± 900
± 900
± 900
± 900
Type
HAS 50-S
HAS 100-S
HAS 200-S
HAS 300-S
HAS 400-S
HAS 500-S
HAS 600-S
RoHS since
date code
45217
45325
45166
45326
45333
45201
45260
VC
Supply voltage (± 5 %) 5)
± 15
V
I
Current consumption
C
± 15
mA
ÎP
Overload capability
30,000
At
V
Rms voltage for AC isolation test, 50 Hz, 1 min
3
kV
d
Vb
Rated isolation voltage rms, safe separation
5001)
V
R
Isolation resistance @ 500 VDC
IS
> 1000 MΩ
VOUT
Output voltage (Analog)@ ± IPN, RL = 10 kΩ, TA = 25°C ± 4V ± 40 mV
R
OUT
Output internal resistance
approx. 100
Ω
RL
Load resistance 6)
>1
kΩ
Accuracy - Dynamic performance data
X
εL
VOE
V
OH
TCVOE
TCVOUT
tr
di/dt
BW
Accuracy @ IPN, TA = 25°C (without offset)
Linearity error 2) (0 .. ± I )
PN
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ I = 0;
P
after an excursion of 1 x IPN
Temperature coefficient of VOE HAS 50-S
HAS 100..600-S
Temperature coefficient of VOUT (% of reading)
Response time to 90% of IP step
di/dt accurately followed
Frequency bandwidth (- 3 dB) 3)
<±1
%
< ± 1 % of I
PN
< ± 20 mV
< ± 20 mV
< ± 2 mV/K
< ± 1 mV/K
< ± 0.1 %/K
<3
µs
> 50
A/µs
DC .. 50 kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
m
Mass
Standards 4)
- 10 .. + 80 °C
- 25 .. + 80 °C
approx. 60
g
EN 50178: 1997
Features
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Isolation voltage 3000 V~
• Low power consumption
•
Extended
measuring
range
(3
x
I)
PN
• Insulated plastic case made of
polycarbonate PBT recognized
according to UL 94-V0
Advantages
• Easy mounting
• Small size and space saving
• Only one design for wide current
ratings range
• High immunity to external
interference.
Applications
• AC variable speed drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
Application Domain
Notes : 1) Pollution class 2, overvoltage category III.
2) Linearity data exclude the electrical offset.
3) Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency.
4) Please consult characterisation report for more technical details and
application advice.
5) Operating at ±12V ≤ Vc < ±15V will reduce the measuring range.
6) If the customer uses 1kΩ of the load resistor, the primary current has to
be limited as the nominal.
• Industrial
061019/7
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/2
www.lem.com