English
Language : 

HAS50-S Datasheet, PDF (1/2 Pages) LEM – Current Transducers HAS 50 to 600-S
Current Transducers HAS 50 to 600-S
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN =
VOUT =
50 .. 600 A
±4V
Electrical data
Primary nominal
r.m.s. current
I (A)
PN
50
100
200
300
400
500
600
Primary current
measuring range
I (A)
P
± 150
± 300
± 600
± 900
± 900
± 900
± 900
Type
HAS 50-S
HAS 100-S
HAS 200-S
HAS 300-S
HAS 400-S
HAS 500-S
HAS 600-S
VC
IC
IOC
Vd
Vb
RIS
VOUT
40
ROUT
RL
mV
Supply voltage (± 5 %)
Current consumption
Overload capacity
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn
R.m.s. rated voltage, safe separation
Isolation resistance @ 500 VDC
Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C
± 15
V
± 15
mA
30,000
At
3
kV
5001)
V
> 1000 MΩ
± 4V ±
Output internal resistance
Load resistance
approx. 100
Ω
>1
kΩ
Accuracy - Dynamic performance data
X
εL
VOE
VOH
VOT
ε TC G
tr
di/dt
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity 2) (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x IPN
Thermal drift of VOE
HAS 50-S
HAS 100 to HAS 600-S
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
di/dt accurately followed
Frequency bandwidth (- 3 dB) 3)
<±1
%
< ± 1 % of IPN
< ± 20
mV
< ± 20
<±2
<±1
< ± 0.1
<3
> 50
DC .. 50
mV
mV/K
mV/K
%/K
µs
A/µs
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
m
Mass
Standards 4)
- 10 .. + 80 °C
- 25 .. + 80 °C
approx. 60
g
EN 50178
Features
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Isolation voltage 3000 V~
• Low power consumption
• Extended measuring range (3 x IPN)
• Insulated plastic case made of
polycarbonate PBT recognized
according to UL 94-V0
Advantages
• Easy mounting
• Small size and space saving
• Only one design for wide current
ratings range
• High immunity to external
interference.
Applications
• AC variable speed drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
Notes : 1) Pollution class 2, overvoltage category III.
2) Linearity data exclude the electrical offset.
3) Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency.
4) Please consult characterisation report for more technical details and
application advice.
LEM Components
981007/4
www.lem.com