HAS-300-S Datasheet, PDF (1/3 Pages) LEM – Current Transducer HAS 50 .. 600-S
Current Transducer HAS 50 .. 600-S
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit and the secondary
circuit.
IPN = 50 .. 600 A
Electrical data
Type
Primary nominal Primary current, RoHS since
current rms measuring range 1) date code
IPN (A)
HAS 50-S
50
IPM (A)
± 150
45217
HAS 100-S
100
± 300
45325
HAS 200-S
200
± 600
45166
HAS 300-S
300
± 900
45326
HAS 400-S
400
± 900
45333
HAS 500-S
500
± 900
45201
HAS 600-S
600
± 900
45260
VC
Supply voltage (± 5 %) 1)
± 15
V
IC
Current consumption
± 15
mA
RIS Isolation resistance @ 500 VDC
> 1000
MΩ
VOUT Output voltage (Analog) @ ± IPN, RL = 10 kΩ, TA = 25°C ± 4V ± 40
mV
ROUT Output internal resistance
approx
100
Ω
RL
Load resistance 2)
> 1
kΩ
Accuracy - Dynamic performance data
X
ε
L
Accuracy @ IPN , TA = 25°C (excluding offset)
Linearity error 3) (0 .. ± IPN)
< ± 1
< ± 1
%
% of IPN
VOE Electrical offset voltage, TA = 25°C
< ± 20
mV
VOH Hysteresis offset voltage @ IP = 0,
after an excursion of 1 x IPN < ± 20
mV
TCVOE Temperature coefficient of VOE HAS 50-S
< ± 2
mV/K
HAS 100 .. 600-S < ± 1
mV/K
TCVOUT Temperature coefficient of VOUT (% of reading)
tr
Response time to 90 % of IPN step
di/dt di/dt accurately followed
< ± 0.1
< 3
> 50
%/K
µs
A/µs
BW Frequency bandwidth (- 3 dB) 4)
DC .. 50
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
m
Mass
approx
Standard
- 10 .. + 80
°C
- 25 .. + 80
°C
60
g
EN 50178: 1997
Notes: 1) Operating at ± 12 V ≤ VC < ± 15 V will reduce the measuring range
2) If the customer uses 1 kΩ of the load resistor, the primary current has to be
limited as the nominal. To measure the full defined measuring range, the
load resistor should be at minimum 10 kΩ
3) Linearity data exclude the electrical offset
4) Please refer to derating curves in the technical file to avoid excessive core
heating at high frequency.
Features
●● Hall effect measuring principle
●● Galvanic isolation between
primary and secondary circuit
●● Low power consumption
●● Extended measuring range
(3 x IPN)
●● Isolated plastic case made of
polycarbonate PBT recognized
according to UL 94-V0.
Advantages
●● Easy mounting
●● Small size and space saving
●● Only one design for wide current
ratings range
●● High immunity to external
interference.
Applications
●● AC variable speed drives
●● Static converters for DC motor
drives
●● Battery supplied applications
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Power supplies for welding
applications.
Application domain
●● Industrial.
25October2012/version 11
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
Page 1/3
www.lem.com