English
Language : 

DKB5-10 Datasheet, PDF (1/2 Pages) LEM – DC Current transducer DK-B5/10
DC Current transducer DK-B5/10
A split core transducer for the electronic measurement DC current,
with galvanic isolation between the primary (High power) and the
secondary circuits (Electronic circuit) with voltage output.
IPN = 50..400A
Electrical data
Primary Nominal Current
IPN (A.t)
50,75,100
100,150,200
150,225,300
200,300,400
50,75,100
100,150,200
150,225,300
200,300,400
Analogue Output Signal 1)
VOUT (V)
0-5
0-5
0-5
0-5
0-10
0-10
0-10
0-10
Type
DK 100 B5
DK 200 B5
DK 300 B5
DK 400 B5
DK 100 B10
DK 200 B10
DK 300 B10
DK 400 B10
Vc Supply voltage
RL Load resistance (max)
Vd Isolation voltage
f
Frequency
Ic
Current consumption (max)
22-26
250
3000
DC
100
V AC/ DC
kΩ
V AC
mA
Accuracy - Dynamic performance data
X
Accuracy @ IPN, TA=25°C
εL
Linearity
tr
Response time @ 90% of I PN
±1
%
± 0.75
%
< 300
mS
General data
TA Ambient operating temperature (0-95% RH)
- 20 .. + 50
°C
TS Ambient storage temperature
- 20 .. + 85
°C
m Mass
120
g
Features
• DC Measurement
• Split core box
• Voltage output
• Jumper selectable ranges
• Panel mounting
• Extended measuring range
Advantages
• Large aperture
• High isolation between primary and
secondary circuits
• Easy to mount
• No insertion losses
Applications
• Battery Banks
- Monitors load current.
- Monitors charging current.
- Verifies operation.
• Transportation
Measures traction power or auxiliary
loads.
• Electric Heating Elements
Faster response than temperature
sensors.
Options on request
• DIN mounting
Note : 1) For 0-3 V output model, no saturation output up to 3.5 V
for 0-5 V output model, no saturation output up to 5.75 V
and for 0-10 V output model, no saturation output up to 11.5 V
LEM Components
040405/5
w w w .lem.com