English
Language : 

DCVT-25V10 Datasheet, PDF (1/2 Pages) LEM – Voltage Transducer DCVT-25V10
Voltage Transducer DCVT-25V10
For the electronic measurement of voltages : DC with a galvanic
isolation between the primary circuit and the secondary circuit.
VPN = 25 V
Preliminary
Electrical data
VPN
Primary nominal r.m.s. voltage
V
Primary voltage, measuring range
P
Vout
Output voltage @ VPN
R
Input Load resistance1)
IN
KN
Conversion ratio
V
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
d
(between primary and measuring circut)
Accuracy - Dynamic performance data
XG
TCVOUT
t
r
Overall accuracy @ VPN TA = 25°C
Output ripple voltage @ V
PN
Thermal drift of VOUT
Response time @ 90 % of V
PN
General data
T
Ambient operating temperature
A
TS
Ambient storage temperature
m
Mass
25
V
+ 1.6 .. + 35
V
10
V
RIN=62(VIN(max)-26.6) Ω
25 : 10
5.4
kV
± 1.5
%
± 50
mV
± 0.1
%/K
150
µs
Features
• RCC voltage transducer
• Compact panel Mount type
Remarks
• When sensing voltages, the range of
the sensed voltage can be adjusted
by adding an external input resistor
on the input side.
Advantages
- 10 .. + 80
- 15 .. + 80
210
• No external power supply is required
• Good overall accuracy
°C • Excellent linearity
°C • Low temperature drift
g • Fast response time
Notes : 1) RIN is not needed whenVP is less than 26.6V.
Power rating of R should be more than 0.02 x V W
IN
IN(max)
Applications
• DC variable inverter
• Railway overhead line voltage
measurement
• Uninterruptible Power Supplies
(UPS)
• Battery supplied application
040302/2
www.nanalem.co.jp