English
Language : 

APR-B10_1 Datasheet, PDF (1/2 Pages) LEM – AC Current transducer
AC Current transducer APR-B10
Split core transducer for the electronic measurement distorted AC
waveforms current, with galvanic isolation between the primary (High
power) and the secondary circuits (Electronic circuit). Switch selectable
ranges and True RMS 0-5V and 0-10V switch selectable voltage output.
I = 10 .. 400 A
PN
Electrical data
Primary Nominal Current
IPN (A.t.RMS)
Analogue Output Signal
VOUT (V)
10,25,50
0-5V or 0-10V
50,75,100
0-5V or 0-10V
100,150,200
0-5V or 0-10V
200,300,400
0-5V or 0-10V
RL
Load resistance
V
Supply voltage
C
IC
Current Consumption
Limitation of voltage output (0-10V)
Limitation of voltage output (0-5V)
Overloaded input current
Type
APR 50 B10
APR 100 B10
APR 200 B10
APR 400 B10
≥ 10
kΩ
+24 ±5% V DC
< 30
mA
14
V
7
V
no limitation
Accuracy-Dynamic performance data
X
εL
VOE
ε VOT
TC G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (±1%)
< ±1
< ±0.5
< ±0.5
±1
% of IPN
% of IPN
% of IPN
mV/K
±0.1
%/K
< 400
ms
30 .. 6000 Hz
General data
T
Ambient operating temperature
A
TS
Ambient storage temperature
m
Mass
Protection type
dCp
Creepage distance
dCl
Clearance distance
CTI
Comparative tracking index (Group I)
UL94 classification
-20 .. +60 °C
-20 .. +85 °C
90
g
IP20
5.5
mm
5.5
mm
600
V
V0
Insulation category
Vb
Rated Voltage
300
V
with IEC 61010-1 standards and following conditions :
- Single insulation
- Over voltage category CAT III
- Pollution degree PD2
- None uniform field
Vd
R.m.s. voltage for AC insulation test, 50Hz, 1mn
5
kV
Ve
R.m.s. voltage for partial discharge extinction @ 10pC 1.5
kV
Vw
Peak impulse withstand voltage 1.2/50µs
6.1
kV
If insulated cable is used for the primary circuit, the voltage category
could be improved with the following table :
Cable insulation (primary)
Category
HAR 05
600V CAT III
HAR 07
1000V CAT III
Notes : Installation and maintenance should be done with power supply disconnected.
The operator must have accrediation to install this material.
The users must take care of all protection gurantee against electrical shock.
LEM Components
Features
• VFD and SCR waveforms current
measurement
• True RMS output
• Split core type
• 5V & 10V switch selectable voltage
output
• DIN mounting & Panel mounting
• Eliminates insertion loss
• Switch selectable ranges
Advantages
• Large aperture for cable up to
Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Applications
• VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
• SCR Controlled Loads:
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs. Current
measurement gives faster
response than temperature
measurement.
• Switching Power Supplies and
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
041029/3