English
Language : 

APR-B10_08 Datasheet, PDF (1/4 Pages) LEM – AC Current transducer
AC Current transducer APR-B10
Split-core transducer for the electronic measurement AC currents (all
waveforms), with galvanic isolation between the primary circuit (high
power) and the secondary circuit (electronics). Switch selectable
measuring ranges and true RMS 0-5V and 0-10V switch selectable
voltage output.
IPN = 10 .. 400 A
Electrical data
Primary Nominal Current
IPN (A.t.rms)
10,25,50
50,75,100
100,150,200
200,300,400
Output Voltage (Analog)
VOUT (V DC)
0-5 or 0-10
0-5 or 0-10
0-5 or 0-10
0-5 or 0-10
Type
APR 50 B10
APR 100 B10
APR 200 B10
APR 400 B10
RoHS since
date code
46184
46304
46194
47150
RL
Load resistance
VC
Supply voltage
IC
Current Consumption
VSL
Output voltage limitation (0-10V)
VSL
Output voltage limitation (0-5V)
ÎP
Overload capability
≥ 10
kΩ
+ 24 ± 5%V DC
< 30
mA
14
V
7
V
no limitation
Accuracy-Dynamic performance data
X
εL
VOE
TCVOE
TCVOUT
tr
BW
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (0 .. ± IPN)
Electrical offset voltage @ TA = 25°C
Temperature coefficient of VOE
Temperature coefficient of VOUT (% of reading)
Response time to 90% of IPN step
Frequency bandwidth (± 1 %)
< ± 1 % of IPN
< ± 0.5 % of IPN
< ± 0.5 % of IPN
±1
mV/K
± 0.1
%/K
< 400
ms
30 .. 6000 Hz
General data
TA
TS
m
IPxx
Ambient operating temperature
Ambient storage temperature
Mass
Protection degree
- 20 .. + 60 °C
- 20 .. + 85 °C
90
g
IP20
Features
• VFD and SCR waveforms current
measurement
• True RMS output (average)
• Split-core type
• 0-5VDC & 0-10VDC switch selectable
voltage output
• DIN rail or Panel mounting
• Switch selectable measuring ranges
• Isolated plastic case recognized
according to UL94-V0.
Advantages
• Large aperture for cable up to
Ø18mm
• High isolation between primary and
secondary circuits
• Eliminates insertion loss
• Easy installation
Applications
• VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
• SCR Controlled Loads:
Acurate measurement of phase
angle fired or burst fired (time
proportioned)
SCRs. Current measurement gives
faster response than temperature
measurement.
• Switching Power Supplies and
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
080212/5
Application domain
• Energy and Automation
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/4